| 2017-07-27 15:15:59 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE |
| | "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING |
| | IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE |
| | REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF |
| | THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. NEC 406.12; FBC RE4002.14, FBC 107.2.1 |
| | 2. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE |
| | AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE |
| | ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT |
| | DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS |
| | REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE |
| | CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12 |
| | 3. PROVIDE GFCI PROTECTED OUTLET IN SHED. NEC |
| | 210.52(G)(1), 210.8; FBC RE3901.9, RE3902.2 |
| | 4. LIGHT IN SHED NEED TO BE CONTROLLED BY A SWITCH. NEC |
| | 210.70(2)(A); FBC RE3903.3 |
| | 5. SHED NEEDS TO HAVE EXTERIOR LIGHT AT ENTRY/EXIT |
| | CONTROLLED BY SWITCH. NEC 210.70(2)(B); FBC RE3903.3 |
| | 6. CIRCUIT 25 SHOWS A #14 WIRE ON A 20 AMP BREAKER. |
| | PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16); FBC |
| | RE3702.13 |
| | 7. CIRCUIT 2,4 SHOWS A #12 WIRE ON A 50 AMP BREAKER. |
| | PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16); FBC |
| | RE3702.13 |
| | 8. CIRCUIT 10,12 SHOWS A #12 WIRE ON A 30 AMP BREAKER |
| | FOR WATER HEATER. PROVIDE CORRECTION. 4500 WATT WATER |
| | HEATER SPECIFIED ON PLUMBING PLAN SHOULD HAVE A 25 AMP |
| | BREAKER. PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16), |
| | 422.13; FBC RE3702.13 |
| | 9. AHU AND CU SPECS SHOW DIFFERENT SIZE CIRCUIT |
| | REQUIREMENTS THAN SHOWN ON PANEL SCHEDULE. PROVIDE |
| | CORRECTION. NEC 110.3, 215.5; FBC 107.2.1 |
| | 10. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220; FBC RE3602.3 |
| | 11. DINING ROOM SHOWS A 15 AMP CIRCUIT. PROVIDE |
| | CORRECTION. NEC 210.52(B)(1); FBC RE3703.2 |
| | 12. COUNTER TOP RECEPTACLES IN THE KITCHEN REQUIRE A |
| | MINIMUM OF TWO 20 AMP CIRCUITS. PROVIDE CORRECTION. NEC |
| | 210.52(B)(1); FBC RE3703.2 |
| | 13. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12 |
| | 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE |
| | LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC |
| | 210.52(F); FBC RE3901.8 |
| | 15. WALL OUTLET IN LAUNDRY IS ON SAME CIRCUIT WITH THE |
| | BATH GFCI OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) |
| | , FBC RE3703.4 |
| | 16. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |