| 2017-08-04 07:48:32 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070343 |
| | ADD: 4601 N. CONGRESS AVE. |
| | CONT: WILSON & COMPANY, INC. |
| | TEL: 407-365-0906 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. AUG.04/ 2017 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED. |
| | |
| | 3) NEW COMMENT. THE CONTRACTOR SUBMITTED A ROOF TOP A/C |
| | STAND PRODUCT APPROVAL NOA 16-0601.01. THE ROOF TOP A/C |
| | STAND PRODUCT APPROVAL A MIAMI-DADE NOA # 16-0601.01 |
| | WAS SUBMITTED, REVIEWED BY THE DESIGNER OF RECORD. |
| | NEITHER THE CONTRACTOR NOR THE DESIGNER OF RECORD HAVE |
| | FOLLOWED THE PRODUCT APPROVAL IN CALCULATING THE AREA |
| | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| | ANCHORS AND UPLIFT VERSES MOMENT. |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |