2017-07-21 16:43:051ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING
 CODES
 PERMIT #17070343
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED
  
 1) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR
 GRAVITY, SHALL BE PROVIDED FOR THE O/A DUCT- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE INDOOR
 UNITS IN THE CEILINGS- SECTION 307.
  
 4) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOFTOP CONDNENSER AND STAND.
 PROVIDE COMPLETE DETAILS FOR ANCHORING INCLUDING HOW
 THE STAND WILL BE ATTACHED TO THE ROOF- SECTION 301.15.
 SUBMIT A MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL FOR
 THE STAND WITH REVIEW STAMP BY THE EOR.
  