| 2017-07-21 16:43:05 | 1ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING | | | CODES | | | PERMIT #17070343 | | | 7/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR | | | GRAVITY, SHALL BE PROVIDED FOR THE O/A DUCT- SECTION | | | C403.2.4.4 FBC-14 ENERGY CONSERVATION. | | | | | | 3) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE INDOOR | | | UNITS IN THE CEILINGS- SECTION 307. | | | | | | 4) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR | | | INSTALLATION OF THE ROOFTOP CONDNENSER AND STAND. | | | PROVIDE COMPLETE DETAILS FOR ANCHORING INCLUDING HOW | | | THE STAND WILL BE ATTACHED TO THE ROOF- SECTION 301.15. | | | SUBMIT A MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL FOR | | | THE STAND WITH REVIEW STAMP BY THE EOR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|