2017-07-17 14:48:222014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070343
 ADD: 4601 N. CONGRESS AVE.
 CONT: WILSON & COMPANY, INC.
 TEL: 407-365-0906
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 17/ 2017
 ACTION: DENIED
  
 1A) SHEET A1 SHOWS A POINT OF SALE THROUGH WINDOWS A &
 B. SHEET A1.1, DEETAIL # 7 INTERIOR WINDOW SCHEDULE
 SHOWS THE BOTTOM OF THESE WINDOWS AT AN ELEVATION 3 FT.
 2 1/2 INCHES. SHEET A-4 DETAIL 7 & 8 SHOW THE ELEVATION
 VIEW OF THESE WINDOW ON BOTH SIDES OF THE GLASS. DETAIL
 # 7 FROM THE CUSTOMER VIEW AND VIEW # 8 FROM THE
 PHARMISTIST POINT OF VIEW. DETAIL #7 INDICATES THE
 BOTTOM OF THE WINDOW/ COUNTER TOP TO BE AT AN ELEVATION
 OF 3 FOOT 4 INCHES DISCREPANCY IN THE PLANS. DETAIL # 8
 IS NOT DIMENSIONED BUT THE WINDOW APPEARS TO HAVE A
 WINDOW FRAME ON THE BOTTOM OF THE WINDOW, A WINDOW
 SILL, WHEN MEASURED THE GLAZING APPEARS TO BE 42 INCHES
 OR 3 FOOR 6 INCHES FROM THE FINISH FLOOR. DISCREPANCY
 IN PLANS, 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) THE PLANS INDICATE THIS IS THE POINT OF SALE,
 WINDOW/ 10 INCH TRANSACTION COUNTER PLEASE PROVIDE A
 CUT SCTION THROUGH THE WINDOW TO INCLUDE THE HEIGHT OF
 THE TRANS ACTION COUNTER IN COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE 904.3.2 COUNTERS. THE COUNTER
 SURFACE HEIGHT SHALL BE 38 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. IF THE POINT OF SALE COUNTER IS
 ALSO TO BE FOR CHECK WRITING THEN A PORTION OF THE
 COUNTER WILL ALSO NEED TO SHOW COMPLIANCE WITH THE
 ACCESS. CODE SECTION 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3. 2014 FBC-ACCESSIBILITY CODE 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2) SHEETS A1-1 AND A4 INDICATE THE USE OF A NEW FIRE/
 SMOKE CURTAIN, THE PLANS STATE TO THE BUILDING
 STANDARD, WHAT IS THE BUILDING STANDARD THAT IS TO BE
 UPHELD? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved