| 2017-08-25 16:32:35 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070327 |
| | ADD: 1885 OKEECHOBEE BLVD. / SUITE 1885 |
| | CONT: DUKE INDIANA CONSTRUCTION |
| | TEL: 954-453-5261 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. AUGUST 25/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) THERE IS ADDITIONAL INFORMATION REQUIRED BY BOTH |
| | BUILDING AND FIRE. THE OCCUPANCY IS DECLARED TO BE A S1 |
| | OCCUPANCY, BUT THE TYPE OF BUSINESS, STORAGE OF |
| | COMBUSTIBLES HAS NOT BEEN DECLARED. WITH THE STORAGE OF |
| | MATTRESSES, (EXAMPLES) FURNITURE OR TIRES WITHIN THE |
| | RACK STORAGE, ADDITIONAL SPRINKLER HEADS MAYBE REQUIRED |
| | WITHIN THE RACKS THEMSELVES. THE EXISTING FIRE |
| | SPRINKLER SYSTEM MAYBE UNDER SIZED FOR THE AMOUNT OF |
| | COMBUSTIBLE FIRE LOADS. |
| | |
| | 1ST ROUND OF COMMENTS. THE LIFE SAFETY PLAN SHEET A203 |
| | SHOWS THERE IS TO BE RACK STORAGE BUT THE PLANS DO NOT |
| | PROVIDE HOW HIGH THE RACK STORAGE WILL BE? THE 2014 |
| | FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | SECTION 105.2 (6) REQUIRES A PERMIT FOR RACK STORAGE |
| | WHEN THE RACKS ARE FIXED IN PLACE AND THE RACKS ARE |
| | OVER 5 FOOT 9 INCHES IN HEIGHT. |
| | |
| | 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE RACK |
| | STORAGE BUT UNTIL THE TYPES OF RACKS, HEIGHT OF RACKS, |
| | IF THE RACKS HAS AERIAL WALKWAYS, FLOOR OF GRID WORK |
| | STEEL, STAIRS, AND THE TYPE OF COMBUSTIBLE IN THE |
| | RACKS, TO MANY UNKNOWNS TO ISSUE A PERMIT FOR THE S1 |
| | OCCUPANCY. FBC-B 903.2.9. |
| | |
| | 1ST ROUND OF COMMENTS. THE LIFE SAFETY PLAN SHEET A203 |
| | ALSO INDICATES MOST OF THE WAREHOUSE TO BE PALLET |
| | STORAGE. THE PLANS DO NOT INDICATE HOW HIGH THE PALLETS |
| | ARE TO BE STORED. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |