Plan Review Notes
Plan Review Notes For Permit 17070291
Permit Number 17070291
Review Stop B
Sequence Number 1
Notes
Date Text
2017-07-13 17:12:202014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070291
 W. P, B. PRIMARY: 16080844
 ADD: 1101 54TH ST.
 CONT: LATITE ROOFING
 TEL: 954-772-3446
 E-MAIL: MIMI@LATITE. COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 13/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE ON ALL OF THE SUBMITTED PRODUCT DATA AND
 ENHANCED FASTENING WAS FIGURED ON A B EXPOSURE. PLEASE
 REVIEW THE APPROVED SET OF PLANS
 SHEET S-1.0 THE SEAL DATE 10/12/2016 REVISION # 2 THE
 WIND EXPOSURE CATEGORY IS LISTED AS A C EXPOSURE. WITH
 THE C EXPOSURE WITH THE MULTIPLIERS FROM TABLE
 1609.7(2) OF THE 2014 FBC-B WILL AFFECT ALL OF THE ROOF
 PRESSURES AND SPACING OF FASTENERS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  