| Plan Review Notes For Permit 17070265 |
| Permit Number |
17070265 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-01 11:30:20 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NEW SHEETS SUBMITTED FOR ELECTRICAL, E0-1 AND E2-1, | | | NOT SIGNED AND SEALED. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. FBC 107.2.1; FS 471 | | | 2. RECEPTACLE CONTROL NOT TO CODE. OFFICES 314 AND 315 | | | DO NOT SHOW ANY CONTROL. BREAK AREA DOES NOT MEET | | | AMOUNT OF CONTROL REQUIRED. BOTH AREAS REQUIRE A | | | MINIMUM OF 50% OF THE OUTLETS CONTROLLED PER ASHRAE | | | 90.1:8.4.2. ADDITIONALLY, PLAN CURRENTLY SHOWS 8 | | | CIRCUITS BEING CONTROLLED BY A 6 POLE CONTACTOR, WHICH | | | WILL OBVIOUSLY NOT WORK. PROVIDE CORRECTIONS. FBC | | | C405.7.1, FBC 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|