2017-07-21 17:13:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070265
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M2.1: THE 16X12 MAIN TRUNK IS UNDERSIZED FOR 1600
 CFMS AT A TYPICAL LOW PRESSURE FRICTION LOSS OF 0.1
 W.G.
  
 2) M2.1: PROVIDE THE FLEX DUCT SIZES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER