| Notes |
| Date |
Text |
| 2017-07-21 17:13:45 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17070265 | | | 7/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M2.1: THE 16X12 MAIN TRUNK IS UNDERSIZED FOR 1600 | | | CFMS AT A TYPICAL LOW PRESSURE FRICTION LOSS OF 0.1 | | | W.G. | | | | | | 2) M2.1: PROVIDE THE FLEX DUCT SIZES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|