| 2017-12-28 17:46:13 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17070253 |
| | 12/28/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION 607.5.4 CONCERNING THE FLEX DUCTS |
| | PENETRATING THE CORRIDOR WALLS AS SHOWN ON SHEETS M.01, |
| | M.02, M.03, & M.04. THE CORRIDOR WALLS HAVE BEEN |
| | DESIGNATED AS SMOKE BARRIERS ON SHEETS A.02, A.03, AND |
| | A.04, AND THEREFORE ONLY STEEL DUCTS WITH THICKNESSES |
| | NO LESS THAN 0.019 INCH (0.48MM) ARE PERMITTED TO |
| | PENETRATE THE WALLS WITHOUT SMOKE DAMPERS- SEE |
| | EXCEPTION 3 AND PROVIDE EITHER SMOKE DAMPERS TO PROTECT |
| | THE PENETRATIONS, OR CHANGE THE DUCTS TO STEEL. |
| | |
| | 2) SHEET M.01: THE AIR BALANCE CALULATION FOR THE |
| | KITCHEN DOES NOT INCLUDE THE HOOD EXHAUST AND SUPPLY |
| | CFMS. |
| | |
| | 3) SHEET M.01: THE CARRIER INFINITY MODEL NO. |
| | 24ANB748A003 IS A 4-TON 17 SEER VARIABLE SPEED UNIT. IT |
| | IS INCORRECTLY LISTED AS IN THE HVAC SCHEDULES AS A |
| | 5-TON, A 3.75-TON, A 3.25 TON, A 4.75 TON, AND A 2.0 |
| | TON UNIT. PLEASE CORRECT THE SCHEDULES AND CORRECT THE |
| | ENERGYGAUGE COMPLIANCE FORM WHICH IS ALSO LISTING |
| | INCORRECT DATA FOR CAPACITIES AND EFFICIENCY RATINGS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |