| 2017-11-02 08:14:36 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: ALL ITEMS EXCEPT # 4 |
| | CORRECTED. SEE ADDITIONAL COMMENTS IN PARANTHESES. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 (RISER DIAGRAM DOES NOT MATCH THE |
| | INSTALLATION SHOWN ON THE PLAN. IS THERE AN 800 AMP |
| | MAIN THAT FEEDS DISCONNECTS FOR EACH PANEL, OR IS THERE |
| | AN MDP PANEL THAT HAS BREAKERS THAT FEED EACH PANEL. A |
| | "CT CAN" DOES NOT HAVE ANY OVERCURRENT PROTECTION |
| | INSIDE. CLARIFY AND/OR CORRECT DISCREPANCIES BETWEEN |
| | PLAN AND RISER DIAGRAM. PROVIDE CALCULATION THAT STATES |
| | THE AVAILABLE FAULT CURRENT FOR EACH PANEL. A NOTE IS |
| | NOT SUFFICIENT COMPLIANCE. NEC 110.9, 110.10, 215.5; |
| | FBC 107.2.1) |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8.CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | 15. CORRECTED. |
| | 16. CORRECTED. |
| | 17. CORRECTED. |
| | 18. CORRECTED. |
| | 19. CORRECTED. |
| | 20. CORRECTED. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |