| 2017-07-19 14:54:51 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE BATHROOMS IN THE ACCESSIBLE UNITS DO NOT COMPLY |
| | WITH FBC ACC 223.2.1 FACILITIES NOT SPECIALIZING IN |
| | TREATING CONDITIONS THAT AFFECT MOBILITY. |
| | IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS |
| | THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER |
| | THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE |
| | MOBILITY FEATURES COMPLYING WITH 805. |
| | |
| | 805.4 TOILET AND BATHING ROOMS. |
| | TOILET AND BATHING ROOMS THAT ARE PROVIDED AS PART OF A |
| | PATIENT OR RESIDENT SLEEPING ROOM SHALL COMPLY WITH |
| | 603.WHERE PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE |
| | LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH |
| | THE APPLICABLE REQUIREMENTS OF 603 THROUGH 610. |
| | |
| | PROVIDE DETAIL SHOWING COMPLIANCE WITH ALL ELEMENTS. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. A-01 FIG. #28 IS FOR THE EXCEPTIONN FOR |
| | RESIDENTIAL DWELLING UNITS AND DOES NOT COMPLY WITH THE |
| | I2 OCCUPANCY THE ACCESSIBLE TOILETS SHALL COMPLY WITH |
| | FBC ACC 604.3.2 WITHOUT EXCEPTIO3. |
| | |
| | 3. THE SHOWERS IN THE ACCESSIBLE BATHROOMS DO NOT |
| | COMPLY WITH FBC ACC 608.2.1 OR 608.2.2 OR 608.2.3 |
| | |
| | 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 |
| | DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 5. ALL GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE PER FBC ACC 609.4 |
| | |
| | 6. SHT. P-01 THE NOTE ON THE FD IN KITCHEN IS CALLING |
| | OUT FOR A BACKFLOW PREVENTER THE FD SHALL BE EQUIPPED |
| | WITH A TRAP PRIMER PLEASE CLARIFY WHAT YOU MEAN BY |
| | BACKFLOW. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. PLEASE PROVIDE CALCULATIONS FOR GREASE INTERCEPTOR. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. THE HORIZONTAL VENTS ON THE WC AND SH IN THE |
| | ACCESSIBLE BATHROOMS ARE NOT COMPLAINT THOSE FIXTURE |
| | ARE VENTED BY THE LAVATORY. PER FBC PL 905.3 AND 905.4 |
| | |
| | 9. A TEST PORT OF A MIN OF 4" IS REQUIRED ON THE OUTLET |
| | OF THE GREASE INTERCEPTOR A 4" TWOWAY CLEAN OUT CAN BE |
| | USED. PER WPB ORD. |
| | |
| | 10. TEMPERED WATER IS REQUIRED AT THE LAVATORY'S IN THE |
| | COMMON BATHROOMS. PER FBC PL 416.5 TEMPERED WATER FOR |
| | PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125 |
| | |
| | 11. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW AT |
| | WATER METER PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |