| 2017-07-17 14:27:28 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES. |
| | PERMIT #17070253 |
| | 7/17/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 2) PROVIDE AN AIR BALANCE CALCULATION FOR THE KITCHEN |
| | AND DINING ROOM AREAS. |
| | |
| | 3) PLACE A NOTE ON THE PLAN INDICATING THAT SEPARATE |
| | PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST AND FIRE |
| | SUPPRESSION SYSTEMS. PLEASE NOTE THAT CONDITIONED |
| | MAKEUP AIR MAY BE REQUIRED FOR THE HOOD EXHAUST- |
| | SECTION 508.1.1. |
| | |
| | 4) FIRE DAMPERS ARE REQUIRED FOR ALL SUPPLY, RETURN, |
| | AND EXHAUST DUCTS AND TRANSFERS THAT ARE PENETRATING |
| | THE FIRE-RATED CORRIDOR WALLS, RESIDENT ROOM WALLS, |
| | OFFICE WALLS, ETC.- SEE SECTION 607.5.2 & 607.5.3. |
| | |
| | 5) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR |
| | SYSTEMS OF ALL OF THE 5.0 TON AIR HANDLERS PER SECTION |
| | 606.2.1. PLEASE NOTE THAT A TYPICAL 5-TON SYSTEM CAN |
| | PRODUCE OVER 2000 CFMS OF SUPPLY AIR. PROVIDE SYMBOLS |
| | ON THE PLANS TO IDENTIFY THE LOCATIONS OF THE DEVICES. |
| | |
| | 6) INDICATE HOW ACCESS FOR SERVICE AND REPLACEMENT OF |
| | THE AIR HANDLERS ABOVE THE CEILING WILL BE |
| | ACCOMPLISHED. SHOW THE LOCATIONS OF ACCESS PANELS AND |
| | PROVIDE DETAILS AND DIMENSIONS- SECTION 306.1. |
| | |
| | 7) VERIFY WITH NOTES, OR PROVIDE CLEARANCE DISTANCE |
| | MEASUREMENTS FOR ALL O/A INTAKE OPENINGS TO EXHAUST |
| | OUTLETS, PROPERTY LINES, AND DRIVE AREAS SUCH AS |
| | DRIVEWAYS OR PARKING LOTS- SECTION 401.4. |
| | |
| | 8) PROVIDE MOTORIZED OR GRAVITY DAMPERS FOR ALL O/A |
| | INTAKE DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | 9) REFER TO SECTION 506.3.13.2 AND PROVIDE THE REQUIRED |
| | CLEARANCE DISTANCE MEASUREMENTS FOR THE HOOD EXHAUST |
| | OUTLET. |
| | |
| | 10) PROVIDE AN ENLARGED KTICHEN PLAN AND EQUIPMENT |
| | SCHEDULE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | ALL COOKING APPLIANCES AND THE EXHAUST HOOD. PLEASE |
| | NOTE THAT COMBUSTION AIR CALCULATIONS ARE REQUIRED FOR |
| | GAS-FIRED APPLIANCES. |
| | |
| | 11) PROVIDE AN AIR DEVICE SCHEDULE. |
| | |
| | 12) M-02: SHOW A MEANS OF RETURN AIR FROM GROUP 106, & |
| | OFFICES 105, 107, & 108- SECTION 601.5. |
| | |
| | 13) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER |
| | SMACNA STANDARDS. |
| | |
| | 14) M-04: PROVIDE THE WIND LOAD DESIGN CRITERIA AND |
| | STRUCTURAL ENGINEERING FOR INSTALLATION OF THE ROOF TOP |
| | CONDENSERS AND ROOF STANDS- SECTION 301.15. SUBMIT A |
| | FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE STANDS |
| | IF APPLICABLE. |
| | |
| | 15) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW SYSTEMS.- SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | PLEASE NOTE THAT FURTHER COMMENTS MAY OCCUR AFTER |
| | CORRECTED PLANS A RE-SUBMITTED. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |