Plan Review Notes
Plan Review Notes For Permit 17070176
Permit Number 17070176
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-07-12 16:14:04FAILED
  
 1. 4 X FEE APPLIED FOR NOT SUBMITTING PLANS AND PERMIT
 FOLLOWING EMERGENCY INSTALLATION. FACP WAS INSTALLED IN
 OCTOBER 2016 (PER OWNER). PLANS AND PERMIT NOT
 SUBMITTED UNTIL UNPERMITTED PANEL WAS DISCOVERED ON AN
 ANNUAL INSPECTION AND OWNER WAS CITED.
  
 2. SUBMITTED PLANS DO NOT DISPLAY THE REQUIRED
 INFORMATION FOR PLAN REVIEW OR INSPECTION. - NFPA 72
 4.5.1.1
  
 3. AS PER NFPA 72 4.5.1.1 - NUMBER AND LOCATIONS OF
 PULL STATIONS? NUMBER, LOCATIONS, AND CANDELLAS OF
 NOTIFICATION APPLIANCES? NUMBER AND LOCATIONS OF TAMPER
 SWITCHES? NUMBER AND LOCATIONS OF WATER FLOW SWITCHES?
 NUMBER OF FLOORS OF BUILDING TO WHICH THE FIRE ALARM
 SYSTEM IS INSTALLED? IS THE FIRE ALARM SYSTEM LOCAL OR
 REMOTELY MONITORED? ETC.
  
 4. REGARDLESS OF ANY EXISTING DEVICES THE ENTIRE SYSTEM
 MUST NOW COMPY WITH THE CURRENT CODE INCLUDING 75DB AT
 PILLOW TOP DUE TO THE INSTALL OF A NEW FACP. - FLORIDA
 ADMINSTRATIVE RULE 69A-48.002
  
 SENT TO ELECTRICAL. GJT