| Plan Review Notes For Permit 17070175 |
| Permit Number |
17070175 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-11-01 16:08:56 | PERMIT # 17070175 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | | | | PER CONVERSATION WITH JESSICA OF JW FIRE: THE SCOPE WAS | | | BEING CHANGED FROM "REPLACE" TO "REPAIR", WITH AN | | | UNDERSTANDING THAT THE PANEL WAS NOT TO BE PHYSICALLY | | | REMOVED FROM IT'S LOCATION, NOR WERE ANY DEVICES TO BE | | | REMOVED OR ADDED. | | | HOWEVER, AFTER SPEAKING WITH INSPECTOR TELFAIR, IT WAS | | | DETERMINED THAT THIS PERMIT APPLICATION WAS A RESULT OF | | | AN ANNUAL FIRE INSPECTION THAT WAS CONDUCTED IN APRIL | | | 2017. DURING THIS INSPECTION THE INSPECTOR NOTICED THAT | | | THE PANEL AT THIS ADDRESS WAS NEW AND AFTER CONDUCTING | | | SOME RESEARCH IT WAS DETERMINED THAT THE PANEL WAS | | | REPLACED/INSTALLED WITHOUT A PERMIT. | | | | | | AT THIS TIME, THE PERMIT STATUS REMAINS AS A FAIL UNTIL | | | THE MATTER IS RESOLVED. ALL OF THE ORIGINAL COMMENTS | | | UNDER THE PLAN REVIEW CONDUCTED ON 7/12/17 REMAIN AND | | | SHALL BE COMPLIED IN ORDER TO RECEIVE APPROVAL FOR THIS | | | PERMIT. | | | | | | INSPECTOR TELFAIR CAN BE REACHED AT [email protected] / | | | 561-804-4753. | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|