| Plan Review Notes For Permit 17070175 |
| Permit Number |
17070175 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-12 16:24:15 | FAILED | | | | | | 1. SUBMITTED PLANS DO NOT DISPLAY THE REQUIRED | | | INFORMATION FOR PLAN REVIEW OR INSPECTION. - NFPA 72 | | | 4.5.1.1 | | | | | | 2. AS PER NFPA 72 4.5.1.1 - NUMBER AND LOCATIONS OF | | | PULL STATIONS? NUMBER, LOCATIONS, AND CANDELLAS OF | | | NOTIFICATION APPLIANCES? NUMBER AND LOCATIONS OF TAMPER | | | SWITCHES? NUMBER AND LOCATIONS OF WATER FLOW SWITCHES? | | | NUMBER OF FLOORS OF BUILDING TO WHICH THE FIRE ALARM | | | SYSTEM IS INSTALLED? IS THE FIRE ALARM SYSTEM LOCAL OR | | | REMOTELY MONITORED? ETC. | | | | | | 3. REGARDLESS OF ANY EXISTING DEVICES THE ENTIRE SYSTEM | | | MUST NOW COMPY WITH THE CURRENT CODE INCLUDING 75DB AT | | | PILLOW TOP DUE TO THE INSTALL OF A NEW FACP. - FLORIDA | | | ADMINSTRATIVE RULE 69A-48.002 | | | | | | SENT TO ELECTRICAL. GJT |
|