| Date |
Text |
| 2017-07-10 08:50:53 | 1) THE SUBMITTED SHEET FOR THE LOCATION OF UNDERGROUND |
| | LP TANK INSTALLATION IS FOR ILLUSTRATIVE PURPOSES ONLY. |
| | THE LOCATION OF THE UNDERGROUND LP TANK SHALL COMPLY |
| | WITH TABLE 6.3.1 OF NFPA 58-11. SHOW THE DISTANCE OF |
| | THE LP TANK FROM THE EXTERIOR WALL OF THE STRUCTURE. |
| | 2) A SHEET HAS BEEN SUBMITTED FOR THE UNDERGROUND TANK |
| | INSTALLATION THAT REFERS TO A "3.2.9.1." WHAT STANDARD |
| | IS THIS TAKEN FROM? THIS DOES NOT APPEAR TO BE FROM |
| | NFPA 58 AND IS THEREFORE UNACCEPTABLE FOR PERMIT |
| | PURPOSES. SUBMIT INFORMATION AS TO THE FOLLOWING: |
| | A) SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY |
| | WITH NFPA 58 SEC. 6.6.6.1. |
| | B) PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR |
| | THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO |
| | BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC. |
| | 6.6.1.6. |
| | C) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| | NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| | MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS |
| | ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER |
| | OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE, |
| | 3) THE COPY OF THE TABLE 402.4 (34) IS FROM AN OUTDATED |
| | FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS THE 2014 |
| | FBC-FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT SIZING |
| | TABLE. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SUBMIT A COMPLETE COPY OF SIZING TABLE 15.1 (A) FROM |
| | NFPA 58-11. THE SUBMITTED COPY HAS THE CORNER CUT OFF |
| | AND THE PSI OF THIS TABLE CANNOT BE DETERMINED. THIS |
| | TABLE IS NOT FROM THE 2011 EDITION. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLE 402.4 |
| | (28) FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| | 6) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATION |
| | SHEETS AND INSTALLATION INSTRUCTIONS FOR THE FISHER |
| | REGULATORS. |
| | 7) REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| | INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| | AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| | THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| | EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| | 8) INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THEOUGH |
| | THE EXTERIOR WILL BE PROTECTED.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |