| 2018-01-08 17:21:27 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17070136 |
| | 1/8/2018 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IT IS ACKNOWLEDGED THAT THE USE OF FLAMEBAR DUCTWORK |
| | TO REPLACE FIRE-RATED SHAFTS IN THE BUILDING HAS BEEN |
| | GRANTED APPROVAL UNDER SECTION 104.11 FBC ALTERNATE |
| | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND |
| | EQUIPMENT BY ROBERT BROWN WPB BUILDING OFFICIAL. THE |
| | APPROVAL, HOWEVER, DOES NOT INCLUDE THE FLAMEBAR DUCTS, |
| | OR ANY OTHER DUCTS, THAT ARE PENETRATING THE INTERIOR |
| | EXIT STAIRWELL SHAFTS IN THE NORTH AND SOUTH CORES. |
| | THIS CONDITION IS CURRENTLY BEING EVALUATED BY THE |
| | BRISTOL DESIGN TEAM AND IS EXCLUDED FROM THIS REVIEW |
| | UNTIL A LATER DATE. |
| | |
| | 2) COMMENT #2 FROM THE 1ST HAS NOT BEEN COMPLETELY |
| | ADDRESSED. I AM UNABLE TO FIND THE SE-1 & SE-2 |
| | IDENTIFICATION LABELS ON SHEETS M2.01, M2.02, & M2.03. |
| | PLEASE SHOW THE LOCATIONS ON THE PLANS. |
| | |
| | 3) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. PER THE |
| | RESPONSE NARRATIVE THE REQUESTED INFORMATION AND |
| | SPECIFICATIONS FOR THE GENERATOR AND EXHAUST FLUE HAVE |
| | BEEN PROVIDED, HOWEVER NO DOCUMENTS HAVE BEEN UPLOADED |
| | FOR REVIEW. |
| | |
| | 4) COMMENT #4 FROM THE 1ST REVIEW HAS NOT BEEN COMPLETE |
| | ADDRESSED. IT APPEARS THAT THE REVISED ENERGY |
| | COMPLIANCE REPORT DOES NOT INCLUDE THE DATA FOR THE NEW |
| | PARKING GARAGE HEAT PUMPS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |