| 2017-08-09 10:56:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FP P 1 & P 2 - THERE APPEARS TO BE |
| | INSUFFICIENT FIRE SPRINKLER COVERAGE OVER THE NEW |
| | RESIDENT STORAGE AREAS. |
| | |
| | THIS WAS DISCUSSED AT THE MOST RECENT MEETING IN JULY. |
| | IT WAS DISCUSSED THAT A FENCE TYPE MATERIAL WILL BE |
| | PLACED OVER THE THE UNITS FOR SECURITY AND SPRINKLER |
| | COVERAGE WOULD NEED TO NE MODIFIED. |
| | |
| | PLEASE PROVIDE FOR PROPER FIRE SPRINKLER COVERAGE OVER |
| | THESE AREAS. |
| | |
| | |
| | |
| | 2) SHEET FP 2.01 - THERE APPEARS TO BE NO FIRE |
| | SPRINKLER COVERAGE OVER THE WOOD DECK FLOORING AREA ON |
| | THE LOBBY SHEETS. |
| | |
| | PER NFPA 1, CHAPTER 13 FIRE PROTECTION SYSTEMS |
| | |
| | 13.3.2.6* EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES, |
| | BALCONIES, DECKS, OR SIMILAR PROJECTIONS. IN BUILDINGS |
| | PROTECTED THROUGHOUT BY AUTOMATIC SPRINKLERS IN |
| | ACCORDANCE WITH NFPA 13, AUTOMATIC SPRINKLER PROTECTION |
| | SHALL BE PROVIDED FOR |
| | THE EXTERIOR SPACES IN ACCORDANCE WITH 13.3.2.6. |
| | |
| | 13.3.2.6.1 UNLESS THE REQUIREMENTS OF 13.3.2.6.2, |
| | 13.3.2.6.3, OR |
| | 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE INSTALLED UNDER |
| | EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES, BALCONIES, |
| | DECKS, OR SIMILAR PROJECTIONS EXCEEDING 4 FT (1.2 M) IN |
| | WIDTH. [13:8.15.7.1] |
| | 13.3.2.6.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | WHERE THE CANOPIES, ROOFS, PORTE-COCHERES, BALCONIES, |
| | DECKS, OR SIMILAR PROJECTIONS ARE CONSTRUCTED WITH |
| | MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, |
| | OR FIRE RETARDANT?TREATED WOOD AS DEFINED IN NFPA 703, |
| | STANDARD FOR FIRE RETARDANT?TREATED WOOD AND FIRE- |
| | RETARDANT COATINGS FOR BUILDING MATERIALS. |
| | [13:8.15.7.2] |
| | |
| | PLEASE PROVIDE THE MATERIAL SPECIFICATIONS OF ALL WOOD |
| | ELEMENTS OF THE FLOORING DESING IN COMPLIANCE WITH THE |
| | ABOVE NOTED CODE. |
| | |
| | |
| | |
| | |
| | 3) SHEET 156 4A 13A - INDICATES THE WOOD DECKING WITH |
| | SUBFLOORING WITH A NOTE CALL-OUT "WOOD FINISH FLOOR, |
| | LANSCAPE DWG" BUT NO DRAWING REFERENCE SHEET. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 4) SHEETS FP P1 & P2 - THERE ARE INTERANL PRIVATE |
| | GARAGES INDICATED WITH THE PARKING GARAGE AREAS. THERE |
| | ARE NO INDICATIONS THAT WHEN THE INTERANL GARAGE DOOR |
| | IS OPEN, THAT FIRE SPRINKLER PROTECTION WILL BE |
| | PROVIDED FOR THE POSSIBLE OBSTRUCTION. |
| | |
| | PLEASE REVIEW AND PROVIDE THE APPLICABLE NOTE. |
| | |
| | |
| | |
| | 5) FIRE SHARES IDENTICAL CONCERNS REGARDING THE FIRE |
| | DAMPERS, GENERATOR EXHAUST. SMOKE CONTROL SYSTEMS BUT |
| | WILL NOT BE DUPLICATED THOSE QUESTIONS. |
| | |
| | FIRE WILL REVIEW THE RE-SUBMITTAL INFORMATION TO |
| | MECHANICAL AND PROVIDE APPLICABLE COMMENTS IF |
| | NECASSARY. |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |