| Plan Review Notes For Permit 17070136 |
| Permit Number |
17070136 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-08-01 16:01:51 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | FOR THE REVISION I WAS MISSING PAGES E6.12, E6.13, | | | E7.02, E7.05, E7.07 FROM WHAT THE NARITIVE SHOWS IN THE | | | PAGE SCHEDULE. REVISION WAS GENERALLY | | | OK FOR THE REVISED PAGES, BUT DID NOTE ALOT OF | | | DISCREPANCIES IN PANEL SCHEDULES AND CIRCUITRY, MISSING | | | CIRCUIT NUMBERS THAT WAS NOT PART OF THE REVISION. | | | | | | | | | FOUND GENERAL DISCREPANCIES BETWEEN PANEL SCHEDULES AND | | | CIRCUITS IN UNITS. THE NOTES SHOW ARC FAULT WHEN | | | CIRCUITS SHOULD BE GFCI PROTECTED. | | | MOST BATHROOMS SHOW AN OUTLET IN THE MIDDLE OF THE | | | BATHROOM COUNTER ON SAME CIRCUIT AS GFIS BUT DOES NOT | | | STATE WHAT IT IS FOR AND IT IS NOT SHOWN | | | TO BE GFCI PROTECTED, ANOTHER NOTE STATES TO PLACE | | | SMOKE ALARMS ON KITCHEN CIRCUIT BUT ARE SHOWN ON | | | BEDROOM CIRCUIT, KITCHEN COUNTERS IN SOME UNITS ARE | | | LACKING THE REQUIRED OUTLET SPACING REQUIRED BY CODE. | | | | | | ONCE I CATCH UP ON MY REGULAR WORK I WILL LOOK THE | | | REVISION OVER AGAIN. | | | | | | JAKE LEAHY | | | | | | . | | | | | | | | | |
|