| 2017-07-07 15:06:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE WAS NO MANUFACTURES SPECIFICATION SHEETS FOR |
| | THE FLOORING OR UNDERLAYMENT PROVIDED WITH THIS |
| | SUBMITAL THAT SHOWS COMPLIANCE WITH THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | PER NFPA 101, CHAPTER 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | SECTION 10.2. |
| | 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| | EXIT ACCESS CORRIDORS AND SPACES NOT SEPARATED FROM |
| | THEM BY WALLS COMPLYING WITH 30.3.6 SHALL BE NOT LESS |
| | THAN CLASS II. |
| | 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | 10.2.7.1 OR 10.2.7.2, AS APPLICABLE. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, |
| | SHALL HAVE A MINIMUM CRITICAL RADIANT FLUX OF 0.1 |
| | W/CM2. |
| | 10.2.7.3* INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED |
| | IN ACCORDANCE WITH 10.2.7.4, BASED ON TEST RESULTS FROM |
| | NFPA 253, STANDARD METHOD OF TEST FOR CRITICAL RADIANT |
| | FLUX OF FLOOR COVERING SYSTEMS USING A RADIANT HEAT |
| | ENERGY SOURCE, OR ASTM E 648, STANDARD TEST METHOD FOR |
| | CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS USING A |
| | RADIANT HEAT ENERGY SOURCE. |
| | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE CLASSIFIED AS |
| | FOLLOWS IN ACCORDANCE WITH THEIR CRITICAL RADIANT FLUX |
| | VALUES: |
| | (1) CLASS I INTERIOR FLOOR FINISH SHALL BE |
| | CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN |
| | 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| | 10.2.7.3. |
| | (2) CLASS II INTERIOR FLOOR FINISH SHALL BE |
| | CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN |
| | 0.22 W/CM2 BUT LESS THAN 0.45 W/CM2, AS DETERMINED BY |
| | THE TEST DESCRIBED IN 10.2.7.3. |
| | |
| | |
| | PLEASE PROVIDE THE SPECIFICATION SHEETS THAT INDICATE |
| | COMPLIANCE. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |