2018-01-10 06:47:551) THE GAS PLAN NOTES THE TOTAL BTU LOAD ON THE SYSTEM
 AS 310,108 BTU'S. PLEASE REFER TO THE MANUFACTURER'S
 SPECIFICATIONS FOR THE APPLIANCES. THE BTU LOAD OF
 310,108 IS INCORRECT.
 EXISTING STOVE: 6 BURNERS AT 18,000 BTU'S PER BURNER =
 108,000 BTU'S
 GAS DRYER: 20,000 BTU'S
 WATER HEATER: 40,000 BTU'S
 POOL HEATER: 250,000 BTU'S
  
 108,000 + 20,000 + 40,000 + 250,000 = 418,0000 BTU'S.
 DO THE MATH.
 2) THE GAS TABLE THAT HAS BEEN SUBMITTED IS NOT
 ACCEPTABLE. THIS TABLE IS NOT FROM A RECOGNIZED
 STANDARD AND DOES NOT LIST THE TYPE OF PIPE. PIPING
 SHALL BE SIZED PER THE 2014 FBC-FUEL GAS CODE.
 3) THE DISTANCE OF THE FURTHEST GAS OUTLET FROM THE GAS
 METER IS SHOWN AS 76 FEET ON THE GAS PLAN. ALL GAS
 PIPING SHALL BE SIZED USING THE 80 FEET DISTANCE COLUMN
 IN THE GAS CODE. BASED ON TABLE 402.4 (2) IN THE GAS
 CODE FOR SCHEDULE 40 METALLIC PIPE, THE MINIMUM SIZE
 PIPE AT THE POUTLET OF THE GAS METER SHALL BE 1 1/4
 INCHES.
 4) THE MINIMUM SIZE PIPE FOR THE CSST TO THE POOL
 HEATER SHALL BE 1 1/4" WITH AN EHD OF 39 IN ACCORDANCE
 WITH THE 2014 FBC-FUEL GAS TABLE 402.4 (15). A 1 INCH
 CSST LINE IS UNDERSIZED AND CANNOT BE USED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  