| 2017-12-20 13:58:36 | 12/20/2017 3RD GAS REVIEW**DENIED** |
| | |
| | COMMENTS FROM LAST REVIEW STILL NOT ADDRESS. NEW |
| | COMMENTS ADDED FOR NEW CSST REVISION AND DRYER THAT IS |
| | NEW AND NOT EXISTING. IT IS ADVISED THAT THE GAS |
| | QUALIFIER CONTACT THIS PLAN EXAMINER TO SET UP A |
| | MEETING EITHER AT CITY HALL ON ON JOB IN ORDER TO |
| | EXPEDITE AND ADDRESS THE COMMENTS |
| | |
| | |
| | 1) PROVIDE ALL SIZING TABLES BEING USED FOR A MATERIAL |
| | BOTH NEW AND EXISTING IF ANY LEFT AND IT MUST SHOW |
| | PRESSURE DROP AND SPECIFIC GRAVITY FGC 402.3. SUBMITTED |
| | SIZING CHART IS MISSING ALL OF THIS INFORMATION.SUBMIT |
| | TWO COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE |
| | THE GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS |
| | SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR |
| | OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| | SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4, |
| | 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1, |
| | G2413.2, & G2413.3 |
| | |
| | 2) NOT ABLE TO READ DRYER INSTALLTION MANUAL AND |
| | EXHAUST CFM. BUILDING PLAN SHOWS ALL NEW GAS EQUIPMENT. |
| | SUBMIT MANUFACTURERS SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 |
| | |
| | 3) RUNNING OF THE CSST IN A PVC SLEEVE UNDER A BUILDING |
| | IS A LAST RESORT AND THE PLUMBING/ GAS CODE OFFICIAL |
| | WILL ONLY ALLOW THE THE PROPOSED DRAWING IF NO OTHER |
| | SAFE MEANS OF RUNNING A NEW LINE EXIST. FROM THIS PLANS |
| | EXAMINER SITE VISITS P.E PIPING CAN BE RAN ALONG THE |
| | SIDE OF BUILDING AROUND THE BACK TO THE PROPOSED |
| | LOCATION OF THE POOL HEATER. FGC 104.1 |
| | |
| | 4) ) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED |
| | GAS APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR. FGC |
| | SEC.304.9.3 OR FBCR G2407.9.3 |
| | |
| | 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.5 (CLOTHES DRYERS) OR |
| | 2014 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). |
| | |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |