| 2017-10-16 15:07:29 | 10/16/17 GAS 2ND REVIEW**DENED*** |
| | |
| | 1) PROVIDE ALL SIZING TABLES BEING USED FOR A MATERIAL |
| | BOTH NEW AND EXISTING IF ANY LEFT AND IT MUST SHOW |
| | PRESSURE DROP AND SPECIFIC GRAVITY FGC 402.3. SUBMITTED |
| | SIZING CHART IS MISSING THIS INFORMATION |
| | |
| | 2) BUILDING PLAN SHOWS ALL NEW GAS EQUIPMENT. SUBMIT |
| | MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION |
| | MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS CODE |
| | SEC. 402.2, AND 301.3 OR 2014 FBC-RES. SEC. G2404.3. |
| | GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1, FBC-RES. SEC.G2408.1 |
| | |
| | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES TO INCLUDE WATER HEATER AS NOW IT WILL BE IN |
| | A CONFINED SPACE INSTEAD OF AN OPEN GARAGE. WHERE |
| | COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. FGC SEC.304.9.3 OR FBCR |
| | G2407.9.3. |
| | |
| | |
| | PLEASE BE ADVISED A STOP WORK ORDER WAS ISSUED ON |
| | 08/22/17 FOR A NEW GAS SYSTEM ON THIS HOME. MOST OF IF |
| | NOT ALL THE PIPING I WAS ABLE TO SEE HAS BEEN REPLACED |
| | AND WILL BE INSPECTED BASED OFF THE 2014 FLORIDA GAS |
| | CODE |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |