2017-10-16 15:07:2910/16/17 GAS 2ND REVIEW**DENED***
  
 1) PROVIDE ALL SIZING TABLES BEING USED FOR A MATERIAL
 BOTH NEW AND EXISTING IF ANY LEFT AND IT MUST SHOW
 PRESSURE DROP AND SPECIFIC GRAVITY FGC 402.3. SUBMITTED
 SIZING CHART IS MISSING THIS INFORMATION
  
 2) BUILDING PLAN SHOWS ALL NEW GAS EQUIPMENT. SUBMIT
 MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2014 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES TO INCLUDE WATER HEATER AS NOW IT WILL BE IN
 A CONFINED SPACE INSTEAD OF AN OPEN GARAGE. WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. FGC SEC.304.9.3 OR FBCR
 G2407.9.3.
  
  
 PLEASE BE ADVISED A STOP WORK ORDER WAS ISSUED ON
 08/22/17 FOR A NEW GAS SYSTEM ON THIS HOME. MOST OF IF
 NOT ALL THE PIPING I WAS ABLE TO SEE HAS BEEN REPLACED
 AND WILL BE INSPECTED BASED OFF THE 2014 FLORIDA GAS
 CODE
  