Plan Review Notes
Plan Review Notes For Permit 17070091
Permit Number 17070091
Review Stop G
Sequence Number 1
Notes
Date Text
2017-07-11 09:27:251.)SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED AND
 ALL PIPE SIZES INCLUDING THE EXISTING GAS SYSTEM., WPB
 AMENDMENTS TO FBC SEC.107.2.1, 107.3.5.3 (12), 2014
 FBC-FUEL GAS SEC. 402.
 3.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 4) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
 5) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
 6) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE POOL
 HEATER ON THE PROPERTY.WPB AMEND. TO FBC SEC.
 107.3.5.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  