| Plan Review Notes For Permit 17070088 |
| Permit Number |
17070088 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-09-22 07:15:53 | PERMIT APPROVED WITH EXCEPTION. THE FOLLOWING ITEMS | | | NEED TO BE CORRECTED AND RE-SUBMITTED BEFORE FIRST | | | INSPECTION: | | | | | | 1. RISER DIAGRAM PROVIDED DOES NOT SHOW THE INTERSYSTEM | | | BONDING TERMINATION POINT REQUIRED. PROVIDE CORRECTION. | | | NEC 250.94; FBC RE3609.3 | | | 2. RESPONSE TO COMMENTS STATES THAT 4 CIRCUIT ARE USED | | | FOR THE DETACHED BUILDING, WHICH IS A CODE VIOLATION. | | | CODE STATES: "A BUILDING OR OTHER STRUCTURE THAT IS | | | SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE | | | OF A SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY | | | ONLY ONE FEEDER OR BRANCH CIRCUIT". PROVIDE CORRECTION. | | | NEC 225.30 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|