Plan Review Notes
Plan Review Notes For Permit 17070066
Permit Number 17070066
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-29 17:06:412ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070066
 8/29/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 BASED ON A MEETING WITH THE CONTRACTOR- FIVE
 CONSTRUCTION- AND A REPRESENTATIVE FROM KANTHAN DESIGN
 CORPORATION THAT OCCURRED ON 8/29/17 PRIOR TO THIS
 REVIEW, IT APPEARS THAT THE RESUBMITTED PLANS FOR THE
 PROPOSED PROJECT ARE MISREPRESENTING THE INTENDED USE
 AND OCCUPANCY OF THE SPACE WHICH WAS REVEALED AT THE
 MEETING TO BE A GYMNASIUM OR EXERCISE FACILITY.
 GYMNASIUM
  
 ARE CLASSIFIED AS ASSEMBLY-3 OCCUPANCIES PER SECTION
 303.4 FBC-14 BUILDING, HOWEVER THE PROJECT IS SPECIFIED
 AS F-1 ON SHEET LS-101. THE FOLLOWING REVIEW COMMMENTS
 ARE BASED ON THIS NEW INFORMATION AS IT APPLIES TO THE
 RESUBMITTED PLANS.
  
 1) SHEET M-2: REVISE THE OUTDOOR AIR CALCULATIONS TO
 INCLUDE THE GYMNASIUM OR EXERCISE AREA- SEE TABLE
 403.3. INDICATE HOW VENTILATION WILL BE PROVIDED FOR
 GYMNASIUM OCCUPANTS.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 PROPOSED SYSTEM IN THE OFFICE- SECTION 312.1.
  
 3) THE ASHRAE 90.1-2010- PRESCRIPTIVE COMPLIANCE OPTION
 ENERGY SUBMITTAL FOR THE OFFICE DOES NOT LIST ANY DATA
 FOR THE THERMAL ENVELOPE OF THE SPACE, IN TERMS OF R OR
 U-VALUES FOR THE ROOF, WALLS, FENESTRATION, DOORS, OR
 FLOOR- SEE SECTION 5.5 AND TABLE 5.5-1 ASHRAE
 90.1-2010.
  
 4) REFER TO SECTION 309.1 AND PROVIDE A SPACE HEATING
 SYSTEMS OR SYSTEMS CAPABLE OF MAINTAINING A MINIMUM
 INDOOR TEMPERATURE OF 68 DEGREES FAHRENHEIT.
  
 5) CONCERNING THE AC WALL BRACKET, PLEASE SEE BUILDING
 REVIEW COMMENT #7 DATED 8/22/17.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  