| 2017-08-29 17:06:41 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17070066 |
| | 8/29/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | BASED ON A MEETING WITH THE CONTRACTOR- FIVE |
| | CONSTRUCTION- AND A REPRESENTATIVE FROM KANTHAN DESIGN |
| | CORPORATION THAT OCCURRED ON 8/29/17 PRIOR TO THIS |
| | REVIEW, IT APPEARS THAT THE RESUBMITTED PLANS FOR THE |
| | PROPOSED PROJECT ARE MISREPRESENTING THE INTENDED USE |
| | AND OCCUPANCY OF THE SPACE WHICH WAS REVEALED AT THE |
| | MEETING TO BE A GYMNASIUM OR EXERCISE FACILITY. |
| | GYMNASIUM |
| | |
| | ARE CLASSIFIED AS ASSEMBLY-3 OCCUPANCIES PER SECTION |
| | 303.4 FBC-14 BUILDING, HOWEVER THE PROJECT IS SPECIFIED |
| | AS F-1 ON SHEET LS-101. THE FOLLOWING REVIEW COMMMENTS |
| | ARE BASED ON THIS NEW INFORMATION AS IT APPLIES TO THE |
| | RESUBMITTED PLANS. |
| | |
| | 1) SHEET M-2: REVISE THE OUTDOOR AIR CALCULATIONS TO |
| | INCLUDE THE GYMNASIUM OR EXERCISE AREA- SEE TABLE |
| | 403.3. INDICATE HOW VENTILATION WILL BE PROVIDED FOR |
| | GYMNASIUM OCCUPANTS. |
| | |
| | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | PROPOSED SYSTEM IN THE OFFICE- SECTION 312.1. |
| | |
| | 3) THE ASHRAE 90.1-2010- PRESCRIPTIVE COMPLIANCE OPTION |
| | ENERGY SUBMITTAL FOR THE OFFICE DOES NOT LIST ANY DATA |
| | FOR THE THERMAL ENVELOPE OF THE SPACE, IN TERMS OF R OR |
| | U-VALUES FOR THE ROOF, WALLS, FENESTRATION, DOORS, OR |
| | FLOOR- SEE SECTION 5.5 AND TABLE 5.5-1 ASHRAE |
| | 90.1-2010. |
| | |
| | 4) REFER TO SECTION 309.1 AND PROVIDE A SPACE HEATING |
| | SYSTEMS OR SYSTEMS CAPABLE OF MAINTAINING A MINIMUM |
| | INDOOR TEMPERATURE OF 68 DEGREES FAHRENHEIT. |
| | |
| | 5) CONCERNING THE AC WALL BRACKET, PLEASE SEE BUILDING |
| | REVIEW COMMENT #7 DATED 8/22/17. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |