| 2017-08-22 10:56:44 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070066 |
| | ADD: 2310 FLORIDA AVENUE |
| | CONT: FIVE CONSTRUCTION |
| | TEL: 561-762-7272 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 11/ 2017 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | |
| | 4) SHEET A-102: |
| | 4A)(1) 2ND REQUEST. PLEASE SHOW THE ACCESSIBLE ROUTE |
| | FROM THE PARKING LOT TO THE LIFT PART OF THE LOADING |
| | DOCK APPROACH PLATFORM. PLEASE NOTE THAT THE LOADING |
| | DOCK IS PART OF A SERVICE ENTRANCE, AN ENTRANCE |
| | INTENDED PRIMARILY FOR DELIVERY OF GOODS OR SERVICES. |
| | PLEASE REVIEW THE DEFINITION FOR PUBLIC ENTRANCE. |
| | AN ENTRANCE THAT IS NOT A SERVICE ENTRANCE OR A |
| | RESTRICTED ENTRANCE. SHOW HOW A PERMANENT AND SAFE |
| | ACCESSIBLE ENTRANCE FOR THE PUBLIC CAN BE MAINTAINED. |
| | |
| | 4A)(2) BUILDING PROVISO: MANUFACTURERS CUT SHEETS WILL |
| | BE REQUIRED, THE PLATFORM LIFT THAT WILL NEED TO MEET |
| | THE REQUIREMENTS OF THE 2014 FBC-ACCESS. CODE 410. |
| | (1-6) AND ASME A 18.1 OR A LULA LIFT AND REQUIRED TO |
| | MEET THE REQUIREMENTS IN THE ACCESS. CODE 408. (1-4.8) |
| | AND ASME A 17.1. |
| | |
| | 4B-4C) COMPLIED. |
| | |
| | 4D) SEMI-COMPLIED. DETAIL A IS OF A GUARDRAIL SYSTEM. |
| | SHEET A-102 SHOWS A GUARDRAIL DETAIL BUT THE NOTES FOR |
| | HEIGHT AND CODE SECTION PROVIDED ARE FOR HANDRAILS |
| | FBC-B 1012.2. GUARDRAIL HEIGHT IS LISTED UNDER |
| | 2014 FBC-B 1013.3. |
| | |
| | 5) SHEET A-301: |
| | 5A) 2ND REQUEST. THE RESPONSE NARRATIVE INDICATES JOIST |
| | LOADING AND OCCUPANCY FOR ENCLOSED MEZZANINE SEE |
| | SECTION A/A-301. SHEET A301 DETAIL A INDICATES AN |
| | ENCLOSED OFFICE 1ST FLOOR, AND AN OPEN MEZZANINE LEVEL |
| | OCCUPANCY S-2 LOW HAZARD. |
| | 5A)(1)PLEASE PROVIDE THE 2ND FLOOR WALL ENCLOSE IF THE |
| | MEZZANINE IS TO BE CONSIDERED ENCLOSED. SEE FBC-B |
| | 505.2.3. PLEASE PROVIDE THE SQUARE FOOTAGE OF MEZZANINE |
| | AND OCCUPANT LOAD? FBC-B TABLE 1004.1.2. |
| | |
| | 5A)(2) IN NEITHER THE FLOOR PLAN A-101 NOR A-103 IS |
| | THERE ANY STAIRS TO GAIN ACCESS TO THE MEZZANINE LEVEL. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5A)(3) SHEET A-103 IT APPEARS TO BE PROVIDING THE LIVE |
| | AND DEAD LOADS OF THE MEZZANINE FLOOR LOADS BUT IS |
| | GIVING ROOF LL: 30 PSF AND DL: 20 PSF. IT WOULD APPEAR |
| | THAT THE DESIGNER OF RECORD IS TAKING VALUES FROM THE |
| | FBC-B TABLE 2308. 102(2) FOR CEILING JOIST SPANS FOR |
| | UNINHABITED ATTICS, LIMITED STORAGE 20 PSF. FOR THE |
| | MEZZANINE LEVEL FOR A STORAGE OCCUPANCY THE DESIGN IS |
| | EITHER 125 PSF LIGHT STORAGE OR DESIGNED TO 250 PSF |
| | HEAVY, 2014 FBC-B TABLE 1607.1(31). |
| | |
| | 5A)(4) PLEASE PROVIDE ENGINEERING CALCULATIONS FOR THE |
| | MEZZANINE STORAGE, FOR THE SIZE AND SPACING OF FLOOR |
| | JOIST, BLOCK WALL MOUNTED FLOOR JOIST HANGERS, LEDGER |
| | AND ANCHORS, AND STRUCTURAL 6 INCH WOOD FRAME (FRT) |
| | WOOD WALL FOR SPACING, SPECIES AND GRADE OF WOOD. THE |
| | FLORIDA BUILDING CODE TABLES FOR FLOOR JOIST SPACING, |
| | AND WEIGHT ARE NOT DESIGNED FOR THE LOADING FOR STORAGE |
| | OCCUPANCY FLOOR SYSTEMS ABOVE GRADE. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4.1 GENERAL. WHEN IT IS REQUIRED |
| | THAT DOCUMENTS BE PREPARED BY A REGISTERED DESIGN |
| | PROFESSIONAL, THE BUILDING OFFICIAL SHALL BE AUTHORIZED |
| | TO REQUIRE THE OWNER TO ENGAGE AND DESIGNATE ON THE |
| | BUILDING PERMIT APPLICATION A REGISTERED DESIGN |
| | PROFESSIONAL WHO SHALL ACT AS THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE. |
| | |
| | 5A)(5) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 106.1 LIVE LOADS POSTED. WHERE THE |
| | LIVE LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A |
| | COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN |
| | DESIGNED TO EXCEED 50 PSF SUCH |
| | DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE |
| | OWNER IN THAT PART OF EACH STORY IN WHICH THEY |
| | APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO |
| | REMOVE OR DEFACE SUCH NOTICES. |
| | |
| | 5A)(6) 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A |
| | CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 |
| | SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, |
| | REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED. |
| | |
| | 5A)(7) THE SHEET A-103 SECTION A SHOWS AN OPEN |
| | MEZZANINE, IF THIS DETAIL IS CORRECT, THEN PLEASE |
| | PROVIDE A GUARDRAIL SYSTEM IN COMPLIANCE WITH GUARDRAIL |
| | HEIGHT IS LISTED UNDER 2014 FBC-B 1013.3. |
| | |
| | 1ST ROUND OF COMMENTS. THE PLANS INDICATE AN EXISTING |
| | OFFICE # 1 BUT THE SECTION DOES NOT INDICATE IF THE |
| | 2X10S ARE CEILING JOIST AND LOAD OR IF THEY ARE TO BE |
| | CONSIDERED AS FLOOR JOIST AND THE LOADING OF THE JOIST? |
| | ADDITIONAL INFORMATION REQUIRED? PLEASE IDENTIFY IF THE |
| | AREA ABOVE THE OFFICE IS TO BE AN ENCLOSED A MEZZANINE, |
| | IF SO THE TYPE OF OCCUPANCY? 107.2.1.3. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 5B) COMPLIED. WALL DETAIL W2/A-501 REMOVED. |
| | |
| | 5C) SEE COMMENTS 5A COVERED UNDER 5A. PLEASE NOTE THE |
| | 2X10 JOIST ARE SPACED AT 16 INCHES ON CENTER WHEREAS |
| | THE STEEL STUDS ARE SPACED AT 24 INCHES ON CENTER, |
| | PLEASE PROVIDE HOW THE LEDGERS ARE GOING TO BE SECURED |
| | TO A NON-STRUCTURAL STUD. PLEASE ALSO PROVIDE WHAT |
| | BUCKET WILL BE USED TO ATTACH THE JOIST TO THE |
| | HORIZONTAL LEDGER AND AT WHAT SPACING THE 2 LEDGERS ARE |
| | TO BE NAILED TOGETHER. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) 2ND REQUEST. SUBMITTED A ENGINEERED ALUMINUM WALL |
| | BRACKET SUPPORT BY FRANK BENNARDO P. E. PLEASE NOTE |
| | STATED RIGHT ON THE DOCUMENT VALID FOR 1PERMITONLY WITH |
| | ORIGINAL ENGINEERS SEAL. |
| | THIS IS NOT A FLORIDA STATE APPROVAL OR MIAMI-DADE NOA. |
| | |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | |
| | 7A) FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE |
| | DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| | WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| | 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | 7B) 61G15-23.002 SEALS ACCEPTABLE TO THE BOARD. WET |
| | SEALS, EMBOSSING SEALS AND DIGITALLY CREATED SEALS |
| | SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER. |
| | |
| | 1ST ROUND OF COMMENTS. MECHANICAL SHEET BY COOL WORLD |
| | SHOWS A NEW CONDENSER MOUNTED ON THE EXTERIOR WALL ON |
| | WALL BRACKETS, THIS IS NOT SHOWN ON ANY OF THE |
| | ARCHITECTURAL PLANS. PLEASE INCORPORATE THE DESIGN AND |
| | PLACEMENT. PLEASE ALSO PROVIDE THE WIND DESIGN CRITERIA |
| | FOR THE MOUNTING OF THE CONDENSER AND BRACKET. |
| | |
| | 7C) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE |
| | WALL MOUNT BRACKET EITHER ON THE STRUCTURAL |
| | SPECIFICATION SHEET G-004 AND OR M-3. 2014 FBC-B |
| | 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION |
| | RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF |
| | WHETHER WIND LOADS GOVERN THE DESIGN OF THE LATERAL |
| | FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | |
| | 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 7.2. RISK CATEGORY. |
| | 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 7D) ONCE THE KNOWN ELEVATION OF THE WALL MOUNTED A/C |
| | CONDENSER AND BRACKETS THEN COMPLIANCE WITH THE |
| | FOLLOWING CODE SECTIONS MAY OR MAY NOT BE REQUIRED. |
| | FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. ACCESS. |
| | |
| | 8) SEMI-COMPLIED. SEE 7A & 7B. 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(G) PRE-ENGINEERED A/C STANDS |
| | |
| | 9) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |