Plan Review Notes
Plan Review Notes For Permit 17070066
Permit Number 17070066
Review Stop P
Sequence Number 1
Notes
Date Text
2017-07-18 08:34:051ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. PER FBC ACC 604.7
  
 2. THE GRAB BARS ARE TO BE MEASURED FROM FINISHED FLOOR
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 3. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL. PER FBC ACC 604.5.1
  
 4. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM)
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. PER FBC
 ACC 604.5.2
  
 5. THE CENTERLINE OF THE WATER CLOSET SHALL BE 16
 INCHES (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION, PER FBC ACC 604.2
  
 6. SHT. P-101 SANITARY RISER THE WC IN THE MENS
 BATHROOM IS NOT VENTED. PER FBC PL 901.2.1
  
 7. SHT. P-101 ON THE SANITARY RISER THE MOPSINK AND
 WATER COOLER SHALL CONNECT TO THE BUILDING DRAIN DOWN
 STREAM OF THE BATHROOM GROUPS. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  