| 2017-07-18 08:34:05 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. PER FBC ACC 604.7 |
| | |
| | 2. THE GRAB BARS ARE TO BE MEASURED FROM FINISHED FLOOR |
| | TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4 |
| | |
| | 3. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| | FROM THE REAR WALL. PER FBC ACC 604.5.1 |
| | |
| | 4. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) |
| | LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE |
| | WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND |
| | 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. PER FBC |
| | ACC 604.5.2 |
| | |
| | 5. THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 |
| | INCHES (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM |
| | FROM THE SIDE WALL OR PARTITION, PER FBC ACC 604.2 |
| | |
| | 6. SHT. P-101 SANITARY RISER THE WC IN THE MENS |
| | BATHROOM IS NOT VENTED. PER FBC PL 901.2.1 |
| | |
| | 7. SHT. P-101 ON THE SANITARY RISER THE MOPSINK AND |
| | WATER COOLER SHALL CONNECT TO THE BUILDING DRAIN DOWN |
| | STREAM OF THE BATHROOM GROUPS. PER FBC PL 912.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |