| 2017-07-14 12:48:01 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17070066 |
| | 7/14/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED AC PLAN MUST BEAR THE SIGNATURE OF THE |
| | PERSON WHO PREPARED THE DESIGN- SECTION 107.2.1 WPB |
| | AMENDMENTS TO THE FBC. |
| | |
| | 2) THE MODEL NUMBER OF THE AIR HANDLER UNT ON THE |
| | SUBMITTED AHRI CERTIFICATE DOES NOT MATCH THE MODEL |
| | NUMBER ON THE AC PLAN- PLEASE CORRECT. |
| | |
| | 3) WIND LOAD ENGINEERING AND SUBMITTAL OF A FL. PRODUCT |
| | APPROVAL OR A MIAMI-DADE NOA ARE REQUIRED FOR |
| | INSTALLATION OF THE CU WALL BRACKET- SECTION 301.5. |
| | |
| | 4) THE LOCATION OF THE OUTSIDE AIR INTAKE IS NOT IN |
| | COMPLAINCE WITH SECTION 401.4 (2) WHICH REQUIRES A 10 |
| | FT. CLEARANCE DISTANCE TO THE LOADING/DRIVE AREA. |
| | ADDITIONALLY PLEASE SEE SECTION 401.5 FOR O/A OPENING |
| | PROTECTION COMPLIANCE. |
| | |
| | 5) PROVIDE A MOTORIZED OR GRAVITY DAMPER FOR THE O/A |
| | INTAKE DUCT- SEE SECTION C403.2.4.4 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | 6) PROVIDE AIR HANDLER INSTALLATION DETAILS AND CLARIFY |
| | HOW ACCESS WILL BE PROVIDED TO THE UNIT PER SECTION |
| | 306.1- PLEASE NOTE THE MAIN PLANS SHOW A DRYWALL |
| | CEILING WHICH MEANS AN ACCESS PANEL WILL HAVE TO BE |
| | INSTALLED. SHOW THE PANEL LOCATION AND PROVIDE |
| | CONSTRUCTION DETAILS. |
| | |
| | 7) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| | DETAILS- SECTION 307. |
| | |
| | 8) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER |
| | SMACNA STANDARDS. |
| | |
| | 9) PROVIDE EXHAUST FAN EQUIPMENT SCHEDULES. |
| | |
| | 10) THE ENGINEER OF RECORD WHO PREPARED THE ENERGY |
| | CALCULATIONS MUST COMPLETE THE MANDATORY REQUIREMENTS |
| | CHECKLIST ON PAGE 7 OF THE ENERGYGAUGE COMPLIANCE |
| | SUBMITTAL. |
| | |
| | 11) THERE IS A SUBMITTAL FOR A GREE DUCTLESS AC SYSTEM. |
| | PLEASE CLARIFY WHERE THIS SYSTEM WILL BE INSTALLED AND |
| | PROVIDE A PLAN. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |