| Plan Review Notes For Permit 17070066 |
| Permit Number |
17070066 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-17 13:52:31 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. SEVERAL MECHANICAL COMPONENTS DESCRIBED IN | | | SUBMITTALS AND THE MECHANICAL PLAN ARE NOT SHOWN ON THE | | | ELECTRICAL PLAN. PROVIDE DETAILS OF ALL WIRING ON | | | ELECTRICAL PLAN. FBC 107.2.1, 107.3.5 | | | 2. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C | | | EQUIPMENT PER CODE. NEC 210.63 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|