Plan Review Notes
Plan Review Notes For Permit 17070066
Permit Number 17070066
Review Stop B
Sequence Number 1
Notes
Date Text
2017-07-11 12:33:372014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070066
 ADD: 2310 FLORIDA AVENUE
 CONT: FIVE CONSTRUCTION
 TEL: 561-762-7272
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 11/ 2017
 ACTION: DENIED
  
 1) SHEET G003:
 1A) DETAIL A- SIGNAGE, DEPICTION SHOWS CHARACTERS BUT
 DOES NOT INCLUDE BRAILLE. PLEASE REVIEW THE
 REQUIREMENTS OF THE 2014 FBC-ACCESS. CODE SECTION
 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND.
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 1B) DETAILS B & C ARE FOR TOILET PAPER DISPENSERS.
 PLEASE PROVIDE COMPLIANCE FOR THE LOCATION OF THE
 DISPENSER BOTH HEIGHT AND THE DISTANCE IN FRONT OF THE
 WATER CLOSET WILL NEED TO SHOW COMPLIANCE WITH
 2014 FBC-ACCESS. CODE 604.9.6 DISPENSERS. TOILET PAPER
 DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 14
 INCHES MINIMUM AND 19 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. THERE SHALL BE A CLEARANCE OF 11/2 INCHES (38
 MM) MINIMUM BELOW THE GRAB BAR. DISPENSERS SHALL NOT BE
 OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 2) SHEET G004:
 2A) UNDER THE HEADING OF GENERAL NOTES INTERIOR
 PARTITIONS THE COMMENT REFERENCES R-4403.7.7 THE
 RESIDENTIAL CODE, PLEASE USE THE 2014 FBC-BUILDING CODE
 FOR ALL CODE REFERENCES. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED, REFERENCING THE WRONG CODE.
  
 2B) UNDER THE HEADING GENERAL NOTES FOR BOTH WOOD AND
 TRUSSES. FOR ANY WOOD THAT IS TO BE USED FOR ANY
 STRUCTURAL ELEMENTS, PLEASE REFER TO FIRE RETARDANT
 TREATED WOOD, THIS BUILDING IS CLASSIFIED AS
 CONSTRUCTION TYPE IIB. PLEASE REVIEW TO FBC-B
 603.1.1.1.3 FIRE-RETARDANT-TREATED WOOD SHALL BE
 PERMITTED IN ROOF CONSTRUCTION, INCLUDING GIRDERS,
 TRUSSES, FRAMING AND DECKING. ALSO REVIEW SHEET A-301
 FOR 2X10 JOIST THAT STATE 2X10 P.T.
  
 3) SHEET A-101 INDICATES A PORTION OF A MEZZANINE BEING
 REMOVED BUT THE PLANS ARE SILENT TO WHERE THERE IS
 STILL APPORTION OF THE MEZZANINE LEFT OVER OFFICE # 1
 AND NONE OF THE PLANS INDICATE HOW TO GAIN ACCESS TO
 THE MEZZANINE AREA THAT IS LEFT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THIS REVIEW CYCLE A THOROUGH
 REVIEW COULD NOT BE COMPLETED AND ADDITIONAL AND OR NEW
 COMMENTS MAY OCCUR ON SUBSEQUENT REVIEWS.
  
 4) SHEET A-102:
 4A) THIS SHEET INDICATES THE INSTALLATION OF A NEW
 LIFT. THE PLANS NEED TO MAKE IT CLEAR IF THIS IS A
 PLATFORM LIFT THAT WILL NEED TO MEET THE REQUIREMENTS
 OF THE ACCESS. CODE 410. (1-6) AND ASME A 18.1 OR A
 LULA LIFT AND REQUIRED TO MEET THE REQUIREMENTS IN THE
 ACCESS. CODE 408. (1-4.8) AND ASME A 17.1.
  
 4B) THE LOADING BAY SHOWS NEW STAIRS, PLEASE PROVIDE
 THE DESIGN MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS
 TABLE 1607.1.(30). SHEET A-502 ALSO SHOWS A STAIR
 SECTION BUT NO LOADING INFORMATION. PLEASE ALSO NOTE
 THE STRINGER INDICATES A 2X12. MUST BE FIRE RETARDANT
 TREATED WOOD. FBC-B 603.1.1.1.3
  
 4C) THE PLANS INDICATE THIS IS A LOADING DOCK, PLEASE
 SHOW WHAT SECTIONS WILL BE REMOVALABLE OR WILL THE
 WHOLE LOADING DOCK HAVE GUARDRAILS SURROUNDING THE
 LOADING DOCK. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4D) DETAIL A IS OF A GUARDRAIL SYSTEM. PLEASE CORRECT
 CODE IN AFFECT, WE ARE NO LONGER UNDER THE 2010 CODE
 AND IN ALL 5 NOTES THE CODE REFERENCE AND NUMBERS ARE
 AGAIN THE RESIDENTIAL CODE NOT THE 2014 FBC-B.
  
 5) SHEET A-301:
 5A) THE PLANS INDICATE AN EXISTING OFFICE # 1 BUT THE
 SECTION DOES NOT INDICATE IF THE 2X10S ARE CEILING
 JOIST AND LOAD OR IF THEY ARE TO BE CONSIDERED AS FLOOR
 JOIST AND THE LOADING OF THE JOIST? ADDITIONAL
 INFORMATION REQUIRED? PLEASE IDENTIFY IF THE AREA ABOVE
 THE OFFICE IS TO BE AN ENCLOSED MEZZANINE, IF SO THE
 TYPE OF OCCUPANCY? 107.2.1.3. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 5B) THERE IS A WALL DETAIL W2/A-501 THAT SHOWS THE WALL
 GOING ALL THE WAY TO THE UNDERSIDE OF THE OF THE ROOF
 DECK. THIS WALL IS CLASSIFIED AS UL DESIGN U465 A 1 HR.
 FIRE RATING NON-BEARING WALL. PLEASE NOTE THIS WALL
 SHOWS NOT ONLY DRYWALL CEILING LOADS BUT 2X10 JOIST,
 NOT KNOWN IF ACTING AS FLOOR JOIST OR CEILING JOIST.
 THE LIMITING HEIGHT REQUIREMENT FOR NON-STRUCTURAL
 INTERIOR WALL, 3 ? INCH STEEL STUD, 25 GAUGE, AT 24
 INCHES ON CENTER WITH A 5 PSF AND L/120 IS LIMITED TO
 13 FOOT 9 INCHES.
  
 5C) PLEASE NOTE THE 2X10 JOIST ARE SPACED AT 16 INCHES
 ON CENTER WHEREAS THE STEEL STUDS ARE SPACED AT 24
 INCHES ON CENTER, PLEASE PROVIDE HOW THE LEDGERS ARE
 GOING TO BE SECURED TO A NON-STRUCTURAL STUD. PLEASE
 ALSO PROVIDE WHAT BUCKET WILL BE USED TO ATTACH THE
 JOIST TO THE HORIZONTAL LEDGER AND AT WHAT SPACING THE
 2 LEDGERS ARE TO BE NAILED TOGETHER. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET A-502 IN THE BOTTOM LEFT SECTION OF THE PAGE
 METHOD OF COMPLIANCE NOTES, FBC 602.1 & 602.1.1 ARE
 BOTH NOTES PULLED FROM THE RESIDENTIAL CODE, NOT
 APPLICABLE UNDER THE 2014 FBC-B. PLEASE CORRECT CODE
 LANGUAGE!!!! 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7) MECHANICAL SHEET BY COOL WORLD SHOWS A NEW CONDENSER
 MOUNTED ON THE EXTERIOR WALL ON WALL BRACKETS, THIS IS
 NOT SHOWN ON ANY OF THE ARCHITECTURAL PLANS. PLEASE
 INCORPORATE THE DESIGN AND PLACEMENT. PLEASE ALSO
 PROVIDE THE WIND DESIGN CRITERIA FOR THE MOUNTING OF
 THE CONDENSER AND BRACKET.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 8) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 9) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  