Plan Review Notes
Plan Review Notes For Permit 17070063
Permit Number 17070063
Review Stop M
Sequence Number 4
Notes
Date Text
2018-01-08 08:34:064TH REVIEW FBC-2014 MECHANICAL
 PERMIT #17070063
 1/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE PAGE 8 OF THE SPARK FIRE RIBBON
 INSTALLATION INSTRUCTIONS WHICH PROVIDES ENCLOSURE
 DIAGRAMS AND REQUIRED OPENINGS THAT THE ARCHITECTURAL
 AND STRUCTURAL ENCLOSURE DRAWINGS ARE NOT CONSISTENT
 WITH.
  
 2) PLEASE NOTE THAT THE RESPONSE LETTER FROM ALLIANCE
 RESIDENTIAL BUILDERS CERTIFYING THE STRUCTURAL DESIGN
 FOR THE FIREPLACE INSTALLATION IS NOT ACCEPTABLE
 BECAUSE THE CONTRACTOR HAS NO AUTHORITY UNDER FLORIDA
 STATUTES TO CERTIFY SUCH AN INSTALLATION. CERTIFICATION
 MUST BE PROVIDED BY THE ENGINEER OF RECORD. PLEASE
 REVIEW AND REVISE THE DRAWINGS TO BE COMPLIANT WITH THE
 MANUFACTURER'S
  
 SPECIFICATIONS, AND PROVIDE A LETTER FROM THE EOR TO
 CERTIFY THE INSTALLATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  