Plan Review Notes
Plan Review Notes For Permit 17070063
Permit Number 17070063
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-09 10:28:392ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070063
 8/9/17
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE 1ST REVIEW COMMENTS STILL EXIST. I AM REPRINTING
 THEM BELOW:
  
 1ST REVIEW FBC-2014 MECHANICAL/FUEL GAS
 PERMIT #17070063
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN
 THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS.
 ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR
 ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE
 BELOW:
  
 621.4 PROHIBITED LOCATIONS.
 UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN
 OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF
 UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION
 303.3.
  
 621.5 ROOM OR SPACE VOLUME.
 THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES
 INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H
 PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR
 SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES
 ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR
 SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF
 COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF
 SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE
 INCLUDED IN THE CALCULATIONS.
  
 621.6 OXYGEN-DEPLETION SAFETY SYSTEM.
 UNVENTED ROOM HEATERS SHALL BE EQUIPPED WITH AN
 OXYGEN-DEPLETION-SENSITIVE SAFETY SHUTOFF SYSTEM. THE
 SYSTEM SHALL SHUT OFF THE GAS SUPPLY TO THE MAIN AND
 PILOT BURNERS WHEN THE OXYGEN IN THE SURROUNDING
 ATMOSPHERE IS DEPLETED TO THE PERCENT CONCENTRATION
 SPECIFIED BY THE MANUFACTURER, BUT NOT LOWER THAN 18
 PERCENT. THE SYSTEM SHALL NOT INCORPORATE FIELD
 ADJUSTMENT MEANS CAPABLE OF CHANGING THE SET POINT AT
 WHICH THE SYSTEM ACTS TO SHUT OFF THE GAS SUPPLY TO THE
 ROOM HEATER.
  
 621.7 UNVENTED DECORATIVE ROOM HEATERS.
 AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE
 INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE
 FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED
 AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127.
  
 621.7.1 VENTLESS FIREBOX ENCLOSURES.
 VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED
 DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING
 WITH ANSI Z21.91.
  
 2) PLEASE NOTE ALL SUBMITTALS FOR MECHANICAL AND FUEL
 GAS BURNING APPLIANCES SHALL BEAR THE SHOP DRAWING
 STAMP AND SIGNATURE OF THE ENGINEER OF RECORD
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  