| 2017-08-16 17:34:00 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | |
| | 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN |
| | THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS. |
| | ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR |
| | ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE |
| | BELOW: |
| | |
| | 621.4 PROHIBITED LOCATIONS. |
| | UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN |
| | OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF |
| | UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION |
| | 303.3. |
| | |
| | 621.5 ROOM OR SPACE VOLUME. |
| | THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES |
| | INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H |
| | PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR |
| | SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES |
| | ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR |
| | SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF |
| | COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF |
| | SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE |
| | INCLUDED IN THE CALCULATIONS. |
| | |
| | 621.7 UNVENTED DECORATIVE ROOM HEATERS. |
| | AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE |
| | INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE |
| | FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED |
| | AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127. |
| | |
| | 621.7.1 VENTLESS FIREBOX ENCLOSURES. |
| | VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED |
| | DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING |
| | WITH ANSI Z21.91. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |