| 2017-07-21 17:32:08 | 1ST REVIEW FBC-2014 MECHANICAL/FUEL GAS |
| | PERMIT #17070063 |
| | 7/21/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE UNVENTED GAS FIREPLACE SHALL NOT BE INSTALLED IN |
| | THE CLUBHOUSE PER SECTION 621.4 FBC-14 FUEL GAS. |
| | ADDITIONAL INFORMATION FOR BOTH THE INDOOR AND OUTDOOR |
| | ROOM HEATERS AND FIREPLACE BOXES IS REQUIRED. SEE |
| | BELOW: |
| | |
| | 621.4 PROHIBITED LOCATIONS. |
| | UNVENTED ROOM HEATERS SHALL NOT BE INSTALLED WITHIN |
| | OCCUPANCIES IN GROUPS A, E AND I. THE LOCATION OF |
| | UNVENTED ROOM HEATERS SHALL ALSO COMPLY WITH SECTION |
| | 303.3. |
| | |
| | 621.5 ROOM OR SPACE VOLUME. |
| | THE AGGREGATE INPUT RATING OF ALL UNVENTED APPLIANCES |
| | INSTALLED IN A ROOM OR SPACE SHALL NOT EXCEED 20 BTU/H |
| | PER CUBIC FOOT (207 W/M3) OF VOLUME OF SUCH ROOM OR |
| | SPACE. WHERE THE ROOM OR SPACE IN WHICH THE APPLIANCES |
| | ARE INSTALLED IS DIRECTLY CONNECTED TO ANOTHER ROOM OR |
| | SPACE BY A DOORWAY, ARCHWAY OR OTHER OPENING OF |
| | COMPARABLE SIZE THAT CANNOT BE CLOSED, THE VOLUME OF |
| | SUCH ADJACENT ROOM OR SPACE SHALL BE PERMITTED TO BE |
| | INCLUDED IN THE CALCULATIONS. |
| | |
| | 621.6 OXYGEN-DEPLETION SAFETY SYSTEM. |
| | UNVENTED ROOM HEATERS SHALL BE EQUIPPED WITH AN |
| | OXYGEN-DEPLETION-SENSITIVE SAFETY SHUTOFF SYSTEM. THE |
| | SYSTEM SHALL SHUT OFF THE GAS SUPPLY TO THE MAIN AND |
| | PILOT BURNERS WHEN THE OXYGEN IN THE SURROUNDING |
| | ATMOSPHERE IS DEPLETED TO THE PERCENT CONCENTRATION |
| | SPECIFIED BY THE MANUFACTURER, BUT NOT LOWER THAN 18 |
| | PERCENT. THE SYSTEM SHALL NOT INCORPORATE FIELD |
| | ADJUSTMENT MEANS CAPABLE OF CHANGING THE SET POINT AT |
| | WHICH THE SYSTEM ACTS TO SHUT OFF THE GAS SUPPLY TO THE |
| | ROOM HEATER. |
| | |
| | 621.7 UNVENTED DECORATIVE ROOM HEATERS. |
| | AN UNVENTED DECORATIVE ROOM HEATER SHALL NOT BE |
| | INSTALLED IN A FACTORY-BUILT FIREPLACE UNLESS THE |
| | FIREPLACE SYSTEM HAS BEEN SPECIFICALLY TESTED, LISTED |
| | AND LABELED FOR SUCH USE IN ACCORDANCE WITH UL 127. |
| | |
| | 621.7.1 VENTLESS FIREBOX ENCLOSURES. |
| | VENTLESS FIREBOX ENCLOSURES USED WITH UNVENTED |
| | DECORATIVE ROOM HEATERS SHALL BE LISTED AS COMPLYING |
| | WITH ANSI Z21.91. |
| | |
| | 2) PLEASE NOTE ALL SUBMITTALS FOR MECHANICAL AND FUEL |