| 2017-07-12 12:24:39 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. ELECTRICAL PLAN REQUIRED TO BE SIGNED AND SEALED BY |
| | DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR |
| | QUALIFIER. FS 471, FAC61G15-23, FBC 107.3.5 |
| | 2. SHOW COMPLIANCE WITH ENERGY CODE FOR LIGHTING: "A |
| | MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| | EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1 |
| | 3. PROVIDE CORRECTED PANEL SCHEDULE. CIRCUIT 22 SHOWS |
| | AS A SMALL APPLIANCE CIRCUIT, BUT IT IS FEEDING OUTDOOR |
| | OUTLETS. CIRCUITS 24, 26, AND 30 SHOULD BE AFCI |
| | PROTECTED CIRCUITS. CIRCUIT 9,11 FOR WATER HEATER |
| | SHOULD BE A 25 AMP BREAKER. NEC 215.5, 408.4, 408.30, |
| | 422.13; FBC 107.2.1, FBC RE3706.1 |
| | 4. WIRE FEEDING INTERIOR PANEL FROM OUTSIDE SERVICE IS |
| | TOO SMALL. 2/0 COPPER CAN ONLY BE USED WHERE IT FEEDS |
| | 100% OF THE LOAD. PROVIDE CORRECTION. NEC 310.15(B)(7); |
| | FBC RE3602.2 |
| | 5. LIGHT IN MASTER CLOSET IS SHOWN AS BEING ON THE SAME |
| | CIRCUIT AS THE BATHROOM GFCI OUTLETS, WHICH IS NOT |
| | PERMITTED PER CODE. PROVIDE CORRECTION. NEC |
| | 210.11(C)(3); FBC RE3703.4 |
| | 6. KITCHEN COUNTER OUTLETS SHOW ONLY ONE CIRCUIT (#20). |
| | CODE REQUIRES MINIMUM OF 2 SMALL APPLIANCE CIRCUITS. |
| | PROVIDE CORRECTION. NEC 210.11(C)(1), 210.52(B)(2); FBC |
| | RE3703.2 |
| | 7. DINING ROOM LIGHT IS SHOWN ON THE SMALL APPLIANCE |
| | CIRCUIT FOR THE DINING AREA, WHICH IS NOT PERMITTED PER |
| | CODE. PROVIDE CORRECTION. NEC 210.11(C)(1), |
| | 210.52(B)(2); FBC RE3703.2 |
| | 8. BATH 2 LIGHT OVER SHOWER SHOWS A STANDARD LIGHT. PER |
| | CODE: "LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| | SUITABLE FOR DAMP LOCATIONS". PROVIDE CORRECTION OR |
| | NOTE TO COMPLY. NEC 410.10(D); FBC RE4003.11 |
| | 9. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED |
| | LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT |
| | BE PERMITTED IN CLOTHES CLOSETS". LIGHT IN MASTER |
| | CLOSET IS NOT SPECIFIED. PROVIDE CORRECTION. NEC |
| | 410.16(B), FBC RE4003.12 |
| | 10. IN SEVERAL LOCATIONS THE OUTLET SPACING IS NOT |
| | WITHIN THE LIMITS PER CODE: "RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| | THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| | FROM A RECEPTACLE OUTLET". PROVIDE CORRECTION. NEC |
| | 210.52; FBC RE3901.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |