| Date |
Text |
| 2017-07-10 14:03:11 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17070021 |
| | ADD: 701 S. ROSEMARY AVE. SUITE: 117 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-856-6655 |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 10/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE VALUATION OF $5,000.00 IS EXTREMELY LOW FOR THE |
| | SCOPE OF WORK OF DEMO BOTH THE WOMENS AND MENS RESTROOM |
| | AND THE INSTALLATION OF NEW FINISHES AND PLUMBING |
| | FIXTURES, LABOR AND MATERIAL, FLOOR, WALL BACKER BOARD |
| | AND TILE FINISHES AS WELL AS LIGHTING. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | 2) A3.0: |
| | 2A) DETAILS 2, 3, 7 & 8 ALL SHOW EITHER ACCESSIBLE |
| | TOILET ROOMS AND OR STALLS. ALL OF THE DETAILS HAVE THE |
| | HEIGHT OF THE WATER CLOSET AS 1 FOOT, 3 INCHES OR 15 |
| | INCHES IN HEIGHT. PLEASE REVIEW SECTION 604.4 SEATS OF |
| | THE 2014 FBC-ACCESS. CODE. 04.4 SEATS. THE SEAT HEIGHT |
| | OF A WATER CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 |
| | INCHES MINIMUM AND 19 INCHES MAXIMUM MEASURED TO THE |
| | TOP OF THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO |
| | A LIFTED POSITION. |
| | |
| | 2B) DETAILS 2, 3, 7 & 8 ALL SHOW EITHER ACCESSIBLE |
| | TOILET ROOMS AND OR STALLS. ALL OF THE DETAILS HAVE THE |
| | HEIGHT OF THE GRAB BARS MEASURED FROM FINISH FLOOR TO |
| | THE CENTERLINE OF THE GRAB BAR. PLEASE NOTE A CHANGE |
| | OCCURRED IN THE 2014 ACCESS. CODE. GRAB BARS ARE TO BE |
| | MEASURED VERTICALLY FROM THE FINISH FLOOR TO THE TOP OF |
| | THE GRASPABLE SURFACE, 33 TO 36 INCHES FROM FINISH |
| | FLOOR. SEE ACCESS. CODE 604.5. |
| | |
| | 2C) DETAILS 2, 3, 7 & 8 ALL SHOW EITHER ACCESSIBLE |
| | TOILET ROOMS AND OR STALLS. ALL OF THE DETAILS ALSO |
| | SHOW THE WATER CLOSET BACK AND SIDE GRAB BARS. NONE OF |
| | THE GRAB BARS SHOW THE DIMENSIONS FOR PLACEMENT. PLEASE |
| | SHOW COMPLIANCE WITH THE 2014 ACCESS. CODE SECTIONS |
| | 604.5.1 SIDE WALL AND 604.5.2 REAR WALL. |
| | |
| | 2D) NONE OF THE DETAILS PROVIDE COMPLIANCE WITH THE |
| | ACCESS. CODE SECTION 609.8 STRUCTURAL STRENGTH. |
| | |
| | 2E) DETAILS 3 & 6 BOTH INDICATE THE MIRROR OVER THE |
| | ACCESSIBLE LAVATORY. THE MIRRORS ARE 40 7/8 INCHES |
| | ABOVE THE FINISH FLOOR. PLEASE NOTE THE MIRRORS DO NOT |
| | INDICATE IF THERE IS A RIM/ TRIM AROUND THE MIRRORS. |
| | THE MIRRORS ARE TO BE MOUNTED TO THE WALL SO THE BOTTOM |
| | EDGE OF THE MIRRORS REFLECTIVE SURFACE IS NO HIGHER |
| | (MAXIMUM) OF 40 INCHES ABOVE THE FINISH FLOOR. 2014 |
| | FBC-ACCESS. CODE 603.3. |
| | |
| | 2F) DETAIL 2 & 7 BOTH SHOW TOILET PAPER DISPENSERS BUT |
| | THE MEASUREMENT FOR THE LOCATION IN FRONT OF THE WATER |
| | CLOSET IS NOT GIVEN, PLEASE PROVIDE COMPLIANCE WITH |
| | 2014 ACCESS. CODE 604.7. |
| | |
| | 2G) DETAIL #5 THE MENS ACCESSIBLE TOILET ROOM SHOWS THE |
| | FLUSH CONTROL ON THE WRONG SIDE OF THE WATER CLOSET. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET. SEE 604.6. |
| | |
| | 2H) DETAILS 2, 5 & 6 ALL SHOW THE LOCATION FOR THE NEW |
| | HAND DRIER. THE PLANS SHOW THE HAND DRIER WITH THE |
| | BOTTOM OF THE HAND DRIER AT AN ELEVATION OF 48 INCHES |
| | ABOVE THE REACH RANGES, SEE 308.2 AND 308.3.FOR REACH |
| | RANGES, ALSO REFER TO 309.(2-4) OPERABLE PARTS. |
| | |
| | 2I) THE PLANS INDICATE THE WATER CLOSET LOCATION IS NOT |
| | TO VARY, BUT THE PLANS SHOULD INDICATE COMPLIANCE WITH |
| | 2014 FBC-ACCESS CODE. WATER CLOSET SHALL BE POSITIONED |
| | WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. |
| | THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION. |
| | |
| | 2J) BATHROOM NOTES AND FIXTURES. THE NOTE INDICATES THE |
| | USE OF 5/8 INCH MOISTURE RESISTANT GYPSUM WALLBOARD. |
| | PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 2509.2 BASE FOR |
| | TILE. GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| | DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| | SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS |
| | BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR |
| | C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | |
| | 2K) TACTILE SIGNAGE INDICATES THE ELEVATION TO BE |
| | CENTER LINED AT 60 INCHES OF THE FLOOR. PLEASE REFER TO |
| | THE 2014 FBC-ACCESS. CODE SECTION 703.4.1 HEIGHT ABOVE |
| | FINISH FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS |
| | SHALL BE LOCATED 48 INCHES (1220 MM) MINIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE |
| | BASELINE OF THE LOWEST TACTILE CHARACTER AND 60 INCHES |
| | (1525 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND |
| | SURFACE, MEASURED FROM THE BASELINE OF THE HIGHEST |
| | TACTILE CHARACTER. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |