| Plan Review Notes For Permit 17061395 |
| Permit Number |
17061395 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-14 08:41:13 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061395 | | | 7/14/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW HEAT PUMPS- SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING | | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|