| Plan Review Notes For Permit 17061395 |
| Permit Number |
17061395 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-13 14:47:52 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. PROVIDE LIGHTING CONTROLS AND CIRCUIT IDENTIFICATION | | | FOR "B" TYPE LIGHT FIXTURES AND "A" TYPE LIGHT FIXTURES | | | IN ROOM 107 AND ADJACENT LOBBY. FBC C405.2.2, FBC | | | 107.2.1 | | | 2. PROVIDE DETAIL OF INTERIOR LIGHTING POWER | | | REQUIREMENTS IN RELATION TO THE CONNECTED INTERIOR | | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC C405.5 | | | 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2 | | | AND ASHREA 90.1: 8.4.2 | | | 4. RISER DIAGRAM SHOWS A 100 AMP DISCONNECT FEEDING | | | PANEL H. THE LOAD ON A PHASE OF PANEL H EXCEEDS THIS | | | RATING. PROVIDE CORRECTION. NEC 110.3, 408.30 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|