2017-07-13 14:47:52CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE LIGHTING CONTROLS AND CIRCUIT IDENTIFICATION
 FOR "B" TYPE LIGHT FIXTURES AND "A" TYPE LIGHT FIXTURES
 IN ROOM 107 AND ADJACENT LOBBY. FBC C405.2.2, FBC
 107.2.1
 2. PROVIDE DETAIL OF INTERIOR LIGHTING POWER
 REQUIREMENTS IN RELATION TO THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC C405.5
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 4. RISER DIAGRAM SHOWS A 100 AMP DISCONNECT FEEDING
 PANEL H. THE LOAD ON A PHASE OF PANEL H EXCEEDS THIS
 RATING. PROVIDE CORRECTION. NEC 110.3, 408.30
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  