| 2017-07-10 07:53:05 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17061395 |
| | ADD: 500 S. AUSTRALIAN AVENUE, SUITE: 100 |
| | CONT: DONNELLAN CONSTRUCTION CORP. |
| | TEL: 954-772-8651 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 10/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) ONLY THE COVERSHEET HAS THE APPROVED SIZE FOR THE |
| | ARCHITECTS SEAL, SHEETS A1-A7.0 ALL HAVE THE ARCHITECTS |
| | SEAL REDUCED TO 1 ? INCHES PLEASE REVIEW FLORIDA |
| | ADMINISTRATIVE CODE ARCHITECT. 61G1-16.002(1) BOTH |
| | SEALS SHALL BE APPROXIMATELY 2" IN DIAMETER WITH TWO |
| | CIRCULAR LINES BETWEEN WHICH LINES SHALL APPEAR, AT THE |
| | TOP, THE WORDS ?STATE OF FLORIDA? AND AT THE BOTTOM THE |
| | WORDS ?REGISTERED ARCHITECT? OR ?REGISTERED INTERIOR |
| | DESIGNER,? WHICHEVER IS APPLICABLE. SEALS STATING |
| | ?LICENSED INTERIOR DESIGNER,? LAWFULLY OBTAINED BY |
| | REGISTERED INTERIOR DESIGNERS PRIOR TO JANUARY 1, 2015, |
| | MAY CONTINUE TO BE LAWFULLY USED. |
| | |
| | 2) SHEET A-3.1 DETAIL G SHOWS WHAT APPEARS TO BE A |
| | MICROWAVE IN THE UPPER CABINETS OVER THE BREAK ROOM |
| | SINK. NO DIMENSION IS GIVEN TO THE BOTTOM SHELF OF THE |
| | UPPER CABINETS, PLEASE PROVIDE COMPLIANCE WITH THE 2014 |
| | FBC-ACCESS. CODE SECTIONS: |
| | 2A) 2014 ACCESS. CODE 308 REACH RANGES |
| | |
| | 2B) 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND |
| | SPACE COMPLYING WITH 305 SHALL BE PROVIDED. |
| | |
| | 2C) 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN |
| | ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308. |
| | |
| | 2D) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE |
| | WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM. |
| | |
| | 3) SHEET A-3.0 DETAIL G SHOWS WHAT APPEARS TO BE A |
| | BREAK ROOM SINK, PLEASE PROVIDE COMPLIANCE WITH THE |
| | 2014 FBC-ACCESS. CODE SECTIONS: |
| | 3A) 606.2 CLEAR FLOOR SPACE. |
| | |
| | 3B) 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE |
| | INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR |
| | COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 3C) 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL COMPLY |
| | WITH 309. HAND-OPERATED METERING FAUCETS SHALL REMAIN |
| | OPEN FOR 10 SECONDS MINIMUM. |
| | |
| | 3D) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY AND |
| | DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES |
| | UNDER LAVATORIES AND SINKS. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |