2017-07-14 08:10:561ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17061394
 7/14/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: REFER TO SECTIONS 809.1 & 809.2 FBC-14
 EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES AFFECTED BY THE
 FLOOR PLAN CHANGES- SEE TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) M1.1: PROVIDE THE NEW FLEX DUCT SIZES, AND THE
 SUPPLY AND RETURN CFMS AT THE NEW ROOM LOCATIONS.
  