| Plan Review Notes For Permit 17061394 |
| Permit Number |
17061394 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-14 08:10:56 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17061394 | | | 7/14/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1.1: REFER TO SECTIONS 809.1 & 809.2 FBC-14 | | | EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES AFFECTED BY THE | | | FLOOR PLAN CHANGES- SEE TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) M1.1: PROVIDE THE NEW FLEX DUCT SIZES, AND THE | | | SUPPLY AND RETURN CFMS AT THE NEW ROOM LOCATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|