Plan Review Notes
Plan Review Notes For Permit 17061394
Permit Number 17061394
Review Stop B
Sequence Number 1
Notes
Date Text
2017-07-10 07:34:502014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17061394
 ADD: 500 S. AUSTRALIAN AVENUE, SUITE: 930
 CONT: DONNELLAN CONSTRUCTION CORP.
 TEL: 954-772-8651
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 10/ 2017
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-3.0 DETAIL G SHOWS WHAT APPEARS TO BE A
 MICROWAVE IN THE UPPER CABINETS OVER THE BREAK ROOM
 SINK. NO DIMENSION IS GIVEN TO THE BOTTOM SHELF OF THE
 UPPER CABINETS, PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-ACCESS. CODE SECTIONS:
 1A) 2014 ACCESS. CODE 308 REACH RANGES
  
 1B) 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND
 SPACE COMPLYING WITH 305 SHALL BE PROVIDED.
  
 1C) 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN
 ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 1D) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 2) SHEET A-3.0 DETAIL G SHOWS WHAT APPEARS TO BE A
 BREAK ROOM SINK, PLEASE PROVIDE COMPLIANCE WITH THE
 2014 FBC-ACCESS. CODE SECTIONS:
 2A) 606.2 CLEAR FLOOR SPACE.
  
 2B) 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2C) 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL COMPLY
 WITH 309. HAND-OPERATED METERING FAUCETS SHALL REMAIN
 OPEN FOR 10 SECONDS MINIMUM.
  
 2D) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY AND
 DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES
 UNDER LAVATORIES AND SINKS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  