 CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN SIGNED AND SEALED BY DESIGN
 PROFESSIONAL OR SIGNED BY THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1,
 FAC61G15-23
 2. PROVIDE PANEL SCHEDULE SHOWING ANY NEW OR ALTERED
 CIRCUITS AND THE APPROPRIATE AFCI OR GFCI PROTECTION AS
 REQUIRED. NEC 215.5, FBC 107.2.1
 3. PROVIDE LOCATION OF EXISTING GFCI OUTLETS IN
 KITCHEN. IF NOT TO CODE CURRENTLY, SHOW AS NEW
 LOCATIONS. NEC 210.52
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  