| 2017-07-12 14:31:06 | | | | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. PROVIDE ELECTRICAL PLAN SIGNED AND SEALED BY DESIGN | | | PROFESSIONAL OR SIGNED BY THE ELECTRICAL CONTRACTOR | | | QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1, | | | FAC61G15-23 | | | 2. PROVIDE PANEL SCHEDULE SHOWING ANY NEW OR ALTERED | | | CIRCUITS AND THE APPROPRIATE AFCI OR GFCI PROTECTION AS | | | REQUIRED. NEC 215.5, FBC 107.2.1 | | | 3. PROVIDE LOCATION OF EXISTING GFCI OUTLETS IN | | | KITCHEN. IF NOT TO CODE CURRENTLY, SHOW AS NEW | | | LOCATIONS. NEC 210.52 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|