Plan Review Notes
Plan Review Notes For Permit 17061373
Permit Number 17061373
Review Stop E
Sequence Number 2
Notes
Date Text
2017-10-24 07:59:52CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 PREVIOUS ELECTRICAL REVIEW COMMENTS NOT ADDRESSED:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INCLUDE PANEL
 SCHEDULE OF EXISTING ELECTRICAL PANEL SHOWING ANY NEW
 OR ALTERED CIRCUITS WITH THE APPROPRIATE AFCI OR GFCI
 PROTECTION PER CODE. SHOW THE REQUIRED 20 AMP CIRCUIT
 TO THE GFCI OUTLET LOCATED WITHIN 3 FEET OF THE SINK.
 PROVIDE FLOOR PLAN OF ENTIRE HOME SHOWING THE LOCATION
 OF ELECTRICAL WORK AND THE EXISTING SMOKE ALARMS. IF
 SMOKE ALARMS ARE NOT PRESENT, OR NOT TO CODE, SHOW AS
 NEW INSTALLATION. FBC 107.2.1, 107.3.5, R314.3,
 RE3902.12, RE3703.4, RE3706.1, RE3902, NEC 210.8,
 210.12, 210.52, 215.5 (PANEL SCHEDULE WAS NOT PROVIDED.
 ALTERED CIRCUITS NOT SHOWN WITH AFCI PROTECTION. GFCI
 OUTLET BY SINK IS SHOWN WITH 14 GUAGE WIRE, WHICH IS
 NOT RATED FOR 20 AMPS. ENTIRE HOME FLOOR PLAN SHOWING
 ALL SMOKE ALARMS NOT PROVIDED.) PROVIDE AS PREVIOUSLY
 REQUESTED.
  
 NEW COMMENT:
  
 2. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  