| 2017-10-24 07:59:52 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | PREVIOUS ELECTRICAL REVIEW COMMENTS NOT ADDRESSED: |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INCLUDE PANEL |
| | SCHEDULE OF EXISTING ELECTRICAL PANEL SHOWING ANY NEW |
| | OR ALTERED CIRCUITS WITH THE APPROPRIATE AFCI OR GFCI |
| | PROTECTION PER CODE. SHOW THE REQUIRED 20 AMP CIRCUIT |
| | TO THE GFCI OUTLET LOCATED WITHIN 3 FEET OF THE SINK. |
| | PROVIDE FLOOR PLAN OF ENTIRE HOME SHOWING THE LOCATION |
| | OF ELECTRICAL WORK AND THE EXISTING SMOKE ALARMS. IF |
| | SMOKE ALARMS ARE NOT PRESENT, OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATION. FBC 107.2.1, 107.3.5, R314.3, |
| | RE3902.12, RE3703.4, RE3706.1, RE3902, NEC 210.8, |
| | 210.12, 210.52, 215.5 (PANEL SCHEDULE WAS NOT PROVIDED. |
| | ALTERED CIRCUITS NOT SHOWN WITH AFCI PROTECTION. GFCI |
| | OUTLET BY SINK IS SHOWN WITH 14 GUAGE WIRE, WHICH IS |
| | NOT RATED FOR 20 AMPS. ENTIRE HOME FLOOR PLAN SHOWING |
| | ALL SMOKE ALARMS NOT PROVIDED.) PROVIDE AS PREVIOUSLY |
| | REQUESTED. |
| | |
| | NEW COMMENT: |
| | |
| | 2. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |