2017-07-20 12:15:20CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INCLUDE PANEL
 SCHEDULE OF EXISTING ELECTRICAL PANEL SHOWING ANY NEW
 OR ALTERED CIRCUITS WITH THE APPROPRIATE AFCI OR GFCI
 PROTECTION PER CODE. SHOW THE REQUIRED 20 AMP CIRCUIT
 TO THE GFCI OUTLET LOCATED WITHIN 3 FEET OF THE SINK.
 PROVIDE FLOOR PLAN OF ENTIRE HOME SHOWING THE LOCATION
 OF ELECTRICAL WORK AND THE EXISTING SMOKE ALARMS. IF
 SMOKE ALARMS ARE NOT PRESENT, OR NOT TO CODE, SHOW AS
 NEW INSTALLATION. FBC 107.2.1, 107.3.5, R314.3,
 RE3902.12, RE3703.4, RE3706.1, RE3902, NEC 210.8,
 210.12, 210.52, 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  