| 2017-07-05 13:24:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED PLANS DO NOT PROVIDE SUFFICIENT |
| | INFORMATION TO DETERMINE COMPLIANCE WITH ANY FIRE CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | |
| | 2) THERE IS NO REFERENCE TO WORK RELATING TO THE FIRE |
| | SPRINKLER SYSTEM. ANY WORK THAT REMOVES AND/OR ADDS |
| | WALLS IN AN EXISTING FIORE SPRINKLED AREA SHALL BE |
| | ELAVUATED FOR CODE COMPLIANT FIRE SPRINKLER PROTECTION. |
| | |
| | ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE |
| | UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED FIRE |
| | SPRINKLER CONTRACTORS. |
| | |
| | PLEASE INDICATE IF THE AREA IS SPRINKLED AND A NOTE OF |
| | SHOP DRAWINGS AS NOTED ABOVE. |
| | |
| | |
| | |
| | 3) IT IS UNCLEAR WHAT WALLS WILL BE REMOVED AND WHAT |
| | WALLS WILL BE INSTALLED WITH THE PROJECT. PLEASE |
| | PROVIDE GREATER DETAIL. |
| | |
| | |
| | |
| | 4) THERE IS NO SPECIFIC ADDRESS IN THE TITLE BLOCK ON |
| | THE PLAN SHEETS. |
| | |
| | PLEASE PROVIDE ON EACH SHEET. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |