| 2017-10-19 10:47:57 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS8US COMMENTS HAVE NOT BEEN |
| | COMPLIED WITH. |
| | |
| | 2ND REQUEST1. THE WASHING MACHINES ON FIRST AND SECOND |
| | FLOOR ARE MISSING FROM RISER DIAGRAMS WATER AND |
| | SANITARY PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.3.5.3(11) |
| | |
| | 2ND REQUEST 2. SHT. A1.03 SHOWS A GAS RANGE M1 AND E1 |
| | SHOW AN ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES |
| | IF NOT GAS |
| | |
| | 2ND REQUEST 3. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1 |
| | SHOW AN ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES |
| | IF NOT GAS |
| | |
| | 2ND REQUEST 4. SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF |
| | THE AC UNITS ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS |
| | WH NORTH OF AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE |
| | EAST WALL P1 SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS |
| | ON THE EAST WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |