| 2017-10-19 10:50:19 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | GAS COMMENTS: PLEASE REMOVE REFERENCE TO GAS APPLIANCES |
| | IF NOT GAS |
| | |
| | 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 PLEASE |
| | REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS |
| | |
| | 2. SHOW LOCATION OF TANKLESS WATER HEATERS ON ELEVATION |
| | PLAN SHT. IN COMPLIANCE OF MANUFACTURE INSTALLATION |
| | GUIDE 4FT FROM OPERABLE WINDOW. PER WPB AMEND TO FBC |
| | 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF |
| | NOT GAS |
| | |
| | 3.SHT. A1.03 SHOWS A GAS RANGE M1 AND E1 SHOW AN |
| | ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF |
| | NOT GAS |
| | |
| | 4. SHT. A1.02 SHOWS A GAS RANGE M1 AND E1 SHOW AN |
| | ELECTRIC RANGE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 PLEASE REMOVE REFERENCE TO GAS APPLIANCES IF |
| | NOT GAS |
| | |
| | 5.SHT. A1.02 SHOWS 2 TANKLESS WH SOUTH OF THE AC UNITS |
| | ON THE EAST WALL M1 AND E1 SHOW 1 TANKLESS WH NORTH OF |
| | AC UNIT AND 1 SOUTH OF THE AC UNIT ON THE EAST WALL P1 |
| | SHOWS 2 TANKLESS WH NORTH OF THE AC UNITS ON THE EAST |
| | WALL. CLARIFY. PER WPB AMEND TO FBC 107.2.1 PLEASE |
| | REMOVE REFERENCE TO GAS APPLIANCES IF NOT GAS |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |