| 2017-10-25 13:44:35 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: PREVIOUS COMMENTS CORRECTED |
| | ARE NOTED AS CORRECTED. COMMENTS THAT NEED FURTHER |
| | CORRECTION HAVE ADDITIONAL INFORMATION IN PARENTHESES. |
| | |
| | 1. PLAN SHOWS 2 SERVICES, WHICH IS NOT PERMITTED PER |
| | CODE. REVISE TO SHOW ONE SERVICE WITH 2 METERS. PROVIDE |
| | NEW RISER DIAGRAM TO MATCH. PROVIDE LOAD CALCULATION |
| | FOR ENTIRE SERVICE, PROVIDE ADEQUATE SIZE CONDUCTOR IN |
| | SERVICE RISER TO ACCOMMODATE LOAD, AND PROPERLY SIZED |
| | GROUNDING ELECTRODE SYSTEM. NEC 230.2, 215.5, 220, |
| | 250.50; FBC RE3601.2, 3602.1, 3608.1 (LOAD CALCULATION |
| | PROVIDED IS FOR A MULTI-FAMILY DWELLING WITH 3 UNITS, |
| | WHICH DOES NOT APPLY WHEN THERE ARE ONLY 2 UNITS. THE |
| | DEMAND FACTOR APPLIED IS NOT PERMITTED FOR THIS. IT |
| | APPEARS THAT THE 3/0 WIRE STATED FOR THE SERVICE RISER |
| | IS OF ADEQUATE SIZE, BUT THE LOAD CALCULATION NEEDS TO |
| | BE ACCURATE.) |
| | 2. CORRECTED |
| | 3. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE |
| | "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING |
| | IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE |
| | REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF |
| | THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. NEC 406.12; FBC RE4002.14 (NOTE 4 HAS BEEN |
| | EDITED, BUT IT STILL STATES THE WRONG CODE REFERENCE. |
| | IT SHOULD BE EITHER NEC 406.12 OR FBC RE 4002.14) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | 14. CORRECTED. |
| | 15. CORRECTED. |
| | 16. CORRECTED. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |