| Plan Review Notes For Permit 17061315 |
| Permit Number |
17061315 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-07-05 09:28:43 | RE-ROOF REVISION , BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- BASE SHEET MECHANICALLY ATTACHED FASTENERS NEED THE | | | WITHDRAWAL RESISTANCE TEST (TAS 105) AS REQUIRED BY | | | NOTE #10 OF FLORIDA PRODUCT APPROVAL FL2533-R17 | | | SUBMITTED. PROVIDE 2 SIGNED AND SEALED COPIES OF THE | | | TEST. SEC. 1609.1 FBC. | | | | | | 2- THE DESIGN PRESSURES FOR SELECTED SYSTEM LWC-33 IS | | | -52.5 PSF. NEED TO PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED | | | BY NOTE #8 OF FLORIDA PRODUCT APPROVAL SUBMITTED. | | | PROVIDE 2 SIGNED AND SEALED CALCULATIONS. NOTE: | | | ENGINEER DOING THE CALCULATIONS TO COORDINATE WITH THE | | | TAS 105 RESULTS AS REQUIRED ON ITEM #1 ABOVE. | | | SEC. 1609.1 FBC | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|